期刊文献+

地铁区间消火栓系统爆管点定位系统研究

Positioning System for Burst Pipe Points in Metro Interval Fire Hydrant Systems
在线阅读 下载PDF
导出
摘要 [目的]地铁区间消火栓系统出现爆管等漏水事故时,列车控制室直接远程关闭消火栓系统进区间主管上的电动阀门,导致整个区间消火栓系统处于无水状态,给运营带来较大安全隐患,故有必要对地铁区间消火栓系统爆管点定位系统进行研究。[方法]提出了在区间消防立管上增加电磁流量计和电接点压力表,以实现爆管点的精确定位的方案。同时,通过BAS(环境与设备监控系统)联动控制,以最快速度远程关闭爆管点前后的电动阀门,从而将对区间消防系统的影响降至最低。阐述了地铁区间爆管点定位系统的总体架构,包括感知层、网络层和应用层三部分。[结果及结论]建立爆管点快速定位系统,远程关闭爆管位置前后阀门,最大程度地减少无消火栓系统保护地段及地铁停运时间,实现地铁区间在爆管等事故发生后的正常运营。 [Objective]When water leakage accidents like pipe bursts occur in the fire hydrant system of metro intervals,the train control room will directly close the electric valves on the main pipeline remotely,cutting off water supply to the entire interval fire hydrant system.This results in significant safety risks for operations.Therefore,it is necessary to study a positioning system for burst pipe points in metro interval fire hydrant systems.[Method]A solution is proposed to install electromagnetic flowmeters and electric contact pressure gauges on interval fire protection risers to enable precise positioning of burst pipe points.Additionally,through linkage with the BAS(building automation system)for environmental and equipment monitoring,electric valves before and after the pipe burst point can be closed remotely and swiftly,minimizing the impact on the interval fire protection system.The overall architecture of the positioning system for burst pipe points in metro intervals is outlined,comprising three layers:perception layer,network layer,and application layer.[Result&Conclusion]A rapid positioning system for burst pipe points is established,enabling the remote closure of valves before and after the burst point location.This approach could minimize unprotected sections of the fire hydrant system and the metro service downtime,ensuring the metro interval resumes normal operations promptly following accidents such as pipe burst.
作者 吴正中 余文举 刘俊萍 李柯 刘宗洲 常军霞 刘超 童俊杰 俞科成 WU Zhengzhong;YU Wenju;LIU Junping;LI Ke;LIU Zongzhou;CHANG Junxia;LIU Chao;TONG Junjie;YU Kecheng(CREEC East China Survey and Design Co.,Ltd.,310009,Hangzhou,China;Zhejiang University of Technology College of Civil Engineering,310014,Hangzhou,China)
出处 《城市轨道交通研究》 北大核心 2025年第3期134-137,共4页 Urban Mass Transit
关键词 地铁 消火栓系统 爆管点 定位 地铁区间 metro fire hydrant system burst pipe point positioning metro interval
  • 相关文献

参考文献2

二级参考文献23

  • 1Al-RAFAI W, BARNES R J. Underlying the performance of real-time software-based pipelineleak-detecttion systems. Pipes & Pipelines International, 1999, Novvember-December: 44 - 51.
  • 2FUKUSHIMA K, MAESHIMA R. Gas pipeline leak detection system using the onlinesimulation method. Computers and Chemical Engineering. 2000,24:453 - 456.
  • 3李树平,刘遂庆.城市给水系统[M].北京:中国建筑工业出版社,2012.
  • 4Mounce S R,Boxall J B,Machell J.Development and verification of an online artificial intelligence system for detection of bursts and other abnormal flows.[J]Journal of Water Resources Planning and Management,2010,136 (3):309.
  • 5Romano M,Kapelan Z,Savic D A.Bayesian-based online burst detection in water distribution systems[C]// Integrating Water Systems.London:CRC Press-Taylor & Francis Group,2010:331-337.
  • 6Nazif S,Karamouz M,Tabesh M,et al.Pressure management model for urban water distribution networks[J].Water Resources Management,2010,24:437.
  • 7Mounce S R,Mounce R B,Boxall J B.Identifying sampling interval for event detection in water distribution networks[J].Journal of Water Resources Planning and Management,2012,138(2):187.
  • 8Rossman LA.EPANET 2 user's manual[M].Cincinnati:National Risk Management Research Laboratory Office of Research and Development U S Environmental Protection Agency,2000.
  • 9Yang X S,Deb S.Cuckoo Search via levy flights[C]//World Congress on Nature & Biologically Inspired Computing.Coimbatore:IEEE,2009:210-214.
  • 10Valian E,Tavakoli S,Mohanna S,et al.Improved cuckoo search for reliability optimization problems[J].Computers & Industrial Engineering,2013,64(1):459.