期刊文献+

核电厂IE级阀门电动装置额定电流值研究

Research on Rated Current Values of Electric Actuators for IE-level Valves in Nuclear Power Plants
在线阅读 下载PDF
导出
摘要 IE级阀门电动装置是核电厂重要的安全设备,与核安全密切相关,如电动装置额定电流值错误,会造成上游保护配置与实际运行电流不匹配,存在阀门误动作风险。阀门电动装置电机属于短时工作制电机,不同于长时工作制的电机,对于额定电流大家有异议也没有相关的标准明确规定选择合适的电流作为额定电流。本文通过对电动装置的特性进行分析,确定合适的额定电流值选择方式,现场根据该方法对电动装置电流值进行校核,为后续核电厂电动装置额定电流值确定提供重要的参考。 The IE-level valve electric actuator is an important safety equipment in nuclear power plants,which is closely related to nuclear safety.If the rated current value of the electric actuator is incorrect,it will lead to the mismatch between the upstream protection configuration and the actual operating current,posing a risk of valve malfunction.The motor of the valve electric actuator belongs to the short-time working system,which is different from the motor of the long-time working system.There are disputes about the rated current,and there are no relevant standards that clearly specify the appropriate current as the rated current.This article analyzes the characteristics of the electric actuator to determine the appropriate selection method for the rated current value.The electric actuator's current value is checked based on this method,providing important references for determining the rated current value of the electric actuator in subsequent nuclear power plants.
作者 杨建松 Yang Jiansong(Chengdu Haiguang Nuclear Power Technology Service Co.,Ltd.,Chengdu,Sichuan,China,610041)
出处 《仪器仪表用户》 2024年第9期38-40,共3页 Instrumentation
关键词 电动装置 电流超标 额定电流 electric actuator overcurrent rated current
  • 相关文献

参考文献2

二级参考文献8

  • 1JB8528-1997,阀门电动装置技术条件[S].
  • 2JB8529-1997,隔爆型阀门电动装置技术条件[S].
  • 3JB2195-77,YDF系列电动阀门用三相异步电动机[S].
  • 4JB2196-77,YBDF-WF系列户外型、防腐、隔爆型电动阀门用三相异步电动机[S].
  • 5GB122222-89.多回转阀门驱动装置的连接[S].
  • 6DIN3210-72,阀门电动装置的连接型式、公称力矩、规格和要求[S]
  • 7GB4942.1-85,外壳防护等级[S].
  • 8JB/T8219-1999,工业过程测量和控制系统用电动执行机构[S].