2020—2021年新冠感染疫情期间烟台市公共场所集中空调通风系统卫生状况调查 被引量:4

Hygienic status of centralized air conditioning and ventilation systems in public places in Yantai City during the SARS-CoV-2 infection epidemic period of 2020-2021
原文传递
导出
摘要 目的监测评估2020—2021年新冠感染疫情期间烟台市公共场所集中空调通风系统卫生状况。方法2020—2021年对116家具有集中空调通风系统的公共场所进行了检测,检测项目包括集中空调送风细菌总数、真菌总数、β溶血性链球菌,风管内表面细菌总数、真菌总数和新冠病毒,冷却水和冷凝水中的嗜肺军团菌等项目。结果2020—2021年两年间公共场所集中空调通风系统检测的合格率分别为39.0%(30/77)、56.4%(22/39),差异无统计学意义(χ^(2)=3.187,P=0.074);不同场所的合格率差异有统计学意义(χ^(2)=11.86,P<0.05),其中商场的合格率最高(65.0%),而娱乐场所和医院合格率较低,分别为0.0%、33.3%;送风和风管内表面的检测样品中均未检出β溶血性链球菌和新冠病毒。空调送风中细菌总数的检测合格率相对较高,为98.2%,风管内表面细菌总数和真菌总数合格率比较低,分别为65.5%和71.6%。结论应加强公共场所集中空调通风系统清洗消毒的监管力度,消除集中空调卫生安全隐患。 Objective To monitor and evaluate the sanitary status of centralized air conditioning and ventilation systems in public places in Yantai City during the SARS-CoV-2 infection epidemic from 2020 to 2021.Methods In 2020-2021,116 public places with centralized air conditioning and ventilation systems were monitored,and the test items included the total number of bacteria,the total number of fungi and Streptococcus hemolyticus in blowing air of centralized air conditioners,the total number of bacteria,the total number of fungi and SARS-Co V-2 on the inner surface of air ducts,and Legionella pneumophila in cooling water and condensed water.Results The qualified rates of testing of centralized air conditioning and ventilation systems in public places in 2020 and 2021 were 39.0%(30/77)and 56.4%(22/39),respectively,showing no statistically significant difference(χ^(2)=3.187,P=0.074).There were significantly differences in the qualified rates of different places(χ^(2)=11.86,P<0.05),among which the qualified rate of shopping malls was the highest(65.0%),but the qualified rates of entertainment places(0.0%)and hospitals(33.3%)were low.Streptococcus hemolyticus and SARS-Co V-2 were not detected in the samples collected from blowing air and the inner surface of air ducts.The qualified rate of the total number of bacteria in blowing air of centralized air conditioners was relatively high(98.2%),but the qualified rates of the total number of bacteria(65.5%)and the total number of fungi(71.6%)on the inner surface of air ducts were relatively low.Conclusion It is necessary to strengthen the supervision of cleaning and disinfection of centralized air conditioning and ventilation systems in public places so as to eliminate the hidden sanitary and safety hazards of centralized air conditioners.
作者 于桂梅 李芸 于涛 王松松 丛静 于树涛 陈富讯 阎西革 YU Gui-mei;LI Yun;YU Tao;WANG Song-song;CONG Jing;YU Shu-tao;CHEN Fu-xun;YAN Xi-ge(Yantai Municipal Center for Disease Control and Prevention,Yantai,Shandong 264003,China)
出处 《实用预防医学》 CAS 2023年第3期287-290,共4页 Practical Preventive Medicine
基金 烟台市科技计划项目(2021YD089) 2017年度山东省医药卫生科技发展计划项目(2017WS570)。
关键词 新型冠状病毒感染 公共场所 集中空调通风系统 细菌总数 真菌总数 SARS-CoV-2 infection public place centralized air conditioning and ventilation system total bacteria total fungi
  • 相关文献

参考文献3

二级参考文献37

  • 1王本利,马小芳,滕伟,史晓燕,胡智慧.青岛市部分中央空调冷却塔水军团菌污染状况调查[J].预防医学文献信息,2004,10(6):692-693. 被引量:30
  • 2姜红梅,刘丹,邹梅,徐东群.大连市公共场所军团菌污染现况调查[J].卫生研究,2006,35(5):612-614. 被引量:7
  • 3杨克敌.环境卫生学[M].6版.北京:人民卫生出版社,2007:15-64.
  • 4Borella P, Montagna M T, Romano-Spica V, et al. Legionella infection risk from domestic hot water[J].Emerg Infect Dis,2004, 10( 3 ): 457-464.
  • 5卫生部.军团病诊断标准及处理原则:WS195-200l[S].北京:中国标准出版社,2004.
  • 6WHO. Legionella and the prevention of legionellosis [M]. India: WHO Press, 2007.
  • 7Hoge C W, Breiman R F. Advances in the epidemieology and control of Legionella infections [J]. Epidemiol Rev, 1991, 13 : 329-340.
  • 8中华人民共和国卫生部.公共场所集中空调通风系统卫生规范:WS394--2012[S].北京:中国标准出版社,2012.
  • 9中华人民共和国卫生部.公共场所集中空调通风系统清洗消毒规范:WS/T396--2012[S].北京:中国标准出版社,2012.
  • 10王怀记,龙一兵,吴林,陈文革,石斌,蒋涛.武汉市公共场所空调冷却塔军团菌污染现状调查研究[J].中国卫生工程学,2008,7(2):72-73. 被引量:7

共引文献30

同被引文献51

引证文献4

二级引证文献3

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部