摘要 高压电缆线路在城市供电体系中的比重越来越大,其交叉互联系统发生异常将造成线路无法投入运行。本文对一起110kV交联聚乙烯高压电缆绝缘接头处同轴电缆的放电故障进行分析,通过分析确定了故障原因为绝缘接头处同轴电缆半导电层剥削不到位,形成半导电尖端,局部电场畸变的同时使内外导体间绝缘阻值大幅降低,加速局部放电的烧蚀损伤,最终导致同轴电缆烧蚀击穿。为此,对接地系统的同轴电缆的施工工艺提出了针对性的要求和改进措施,对于提高电缆线路的供电可靠性具有重要意义。 The The proportion of high-voltage cable lines in the urban power supply system is increasing,but the abnormality of the cross-connected system will cause the line to be put into operation.In this paper,the discharge fault of a coaxial cable at 110kV XLPE high-voltage cable insulation joint is analyzed.The cause of the fault is that the semi-conducting layer of the coaxial cable is not stripped at the insulation joint,forming a semi-conductive tip and local electric field distortion.At the same time,the insulation resistance between the inner and outer conductors is greatly reduced,and the ablation damage of the partial discharge is accelerated,eventually leading to ablation breakdown of the coaxial cable.For this reason,the specific requirements and improvement measures for the construction process of the coaxial cable of the grounding system are put forward,which is of great significance for improving the power supply reliability of the cable line.
作者 吴科 乔运松 熊刚 殷业成 王东 Wu Ke;Qiao Yunsong;Xiong Gang;Yin Yecheng;Wang Dong(State Grid Chongqing Electric Power Company Maintenance Branch,Chongqing 400039)
出处 《电气技术》 2020年第6期83-87,共5页 Electrical Engineering
关键词 交叉互联 同轴电缆 半导电层 局部放电 cross-connect coaxial cable semi-conductive layer partial discharge
  • 相关文献

参考文献17

二级参考文献140

共引文献254

同被引文献127

引证文献8

二级引证文献30

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部