一起换流站交流滤波器用断路器合闸失败案例分析 被引量:1

Case analysis of circuit breaker closing failure in AC filter branch in converter stations
在线阅读 下载PDF
导出
摘要 换流站交流滤波器支路需要频繁投切满足无功平衡需求,导致了该支路断路器操作次数多,故障概率大,目前已有多起断路器爆炸事故报道,但故障机理尚未明确。本文基于某换流站交流滤波器用断路器实际合闸故障案例,描述了故障过程和故障后现场检查情况,从合闸电流幅值、相对合闸时间差和分闸电流等不同角度分析了故障前断路器的运行状况并统计了其变化规律,探讨了基于单纯电气量实施断路器运行状态评价的可行性及存在的技术挑战。 The real-time reactive power balance in HVDC substation requires frequent switching of circuit breaker (CB) in AC filter branch. So it is easy to cause the failure of CB. In this paper, a true CB failure case is present, the fault report and scene inspection status are described at first, and then the pre-fault conditions of CB are analyzed from different viewpoints, including the closing currents' amplitudes, differences of relative closing time and magnitudes of CB opening currents. At last, the possibility and existing technical challenges of CB operation status evaluation based on real-time monitoring data are discussed.
作者 傅坚 王宾 周孝法 魏向向 FU Jian;WANG Bin;ZHOU Xiao-fa;WEI Xiang-xiang(State Grid Shanghai Electric Power Company Maintenance Company,Shanghai 200063,China;Department of Electrical Engineering,Tsinghua University,Beijing 100084,China;College of Infomlation and Electrical Engineering,China Agricultural University,Beijing 100083,China)
出处 《电工电能新技术》 CSCD 北大核心 2018年第6期73-78,共6页 Advanced Technology of Electrical Engineering and Energy
基金 国家自然科学基金项目(51477084) 国网上海市电力公司科技项目(SGSHJX00ZSJS1600747)
关键词 高压直流输电 交流滤波器 换流站 断路器合闸故障 合闸电流幅值 HVDC AC filter convertor station CB closing failure closing currents' amplitude
  • 相关文献

参考文献16

二级参考文献196

共引文献394

同被引文献19

引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部