摘要
普光气田天然气净化厂空气中含有一定量的H_2S和SO_2,空调设备腐蚀严重,且现有暖通系统存在一定缺陷。为提高中控室暖通系统运行效果,满足人员和设备对温度和湿度的需求,拟对原暖通系统进行技术优化。中控室内部的设备类和人员类房间分别设置独立的风道系统,实现供冷"人机分离";更换6台恒温恒湿机组和3套多联空调机组,选用高效化学新风净化机组,增设3套消防排烟系统,以满足中控室内部工作人员和设备对安全运行的需求。
Since air in natural gas purification plant of Puguang gas field contains a certain amount of H_2S and SO_2,corrosion of air conditioning equipment is serious.Besides,there are some defects in existing HVAC system.In order to improve the running effect of HVAC system and meet the needs of personnel and equipment to temperature and humidity,the technology optimization of the HVAC system was conducted.In details,separate air duct system was installed in the equipment room and staff room of the central control chamber respectively to realize the cooling by " man-machine separation";six constant temperature and humidity units and more than three sets of air conditioning unit were replaced,as well as the adoption of efficient chemical air purification unit and the addition of three sets of fire smoke exhaust system,so as to satisfy the demand of the internal staff and equipment for safe operation.
出处
《石油与天然气化工》
CAS
北大核心
2018年第1期110-114,共5页
Chemical engineering of oil & gas
关键词
恒温恒湿空调系统
多联机空调系统
消防排烟系统
人机分离
constant temperature and humidity air-conditioning system
VRF air conditioning system
fire smoke exhaust system
man-machine separation