期刊文献+

百万千瓦火电机组一次风自适应系统应用研究 被引量:3

Application Study on an Adaptive Control System of Primary Air Pressure in 1000MW Unit
在线阅读 下载PDF
导出
摘要 为降低一次风机电耗,设计并实施了一次风压自适应控制系统,通过在原有一次风压设定值的基础上,再叠加一个独立的自适应一次风压力偏置值回路,在保证制粉系统安全运行的前提下,逐步降低一次风机出口压力,达到一次风机经济运行的目的。锅炉运行一次风压的降低,可使空气预热器漏风率有所下降,引风机电耗也会相应下降,节能降耗效果明显。 To reduce the power consumption of primary air fans , an adaptive conair pressure was designed and applied by adding an independent adaptive primary air pressure bias circuitbased on the original setting value, thus gradually reducing the primary air pressure and the powerconsumption of primary air fans under the premise of ensuring the safe operation of the coal pulverizingsystem. Meanwhile both the air preheater leakage rate and the power consumdrop accordingly due to the reduction of primary air pressure,resulting in obvious energy
作者 林典鹏 王楚鸿 李大吉 江永 Lin Dianpeng;Wang Chuhong;Li Daji;Jiang Yong(Huaneng Haimen Power Plant , Shantou 515132 , Guangdong Province , China)
机构地区 华能海门电厂
出处 《发电设备》 2017年第6期403-406,共4页 Power Equipment
关键词 一次风压 自适应 控制策略 节能 primary air pressure adaptive system control strategy energy saving