期刊文献+

多并网逆变器系统阻抗建模及谐振特性分析 被引量:3

Impedance Model and Resonance Characteristic Analysis of System With Grid-connected Multiple Inverter
在线阅读 下载PDF
导出
摘要 擒要:多并网逆变器系统的谐振给逆变器的稳定性和电网的电能质量带来了诸多问题。为解决谐振带来的各种问题,建立了多型并网逆变器系统阻抗模型,基于阻抗模型分析了系统谐振机理,研究了谐振特性和并网逆变器数量及电网强度的关系。并以两台并网逆变器系统为例,仿真和实验结果证明了模型的可用性和谐振分析结果的正确性。 The resonance of grid-connected system with the grid-connected multiple inverter bring challenges to the stability of the inverter and power quality of the grid.In order to solve various problems caused by resonance,the impedance model of the system is established and the resonance mechanism of the system is analyzed based on the model.On the basis of mechanism analysis,the relationship among the resonance characteristic ,the number of grid connected inverters and grid strength are studied.And two grid-connected inverters system as an example, simulation and experimental results verify the availability of the model and the accuracy of analytical results.
出处 《电力电子技术》 CSCD 北大核心 2016年第9期64-66,78,共4页 Power Electronics
基金 国家自然科学基金(51277137,51177113)~~
关键词 逆变器 阻抗 谐振 inverter impedance resonance
  • 相关文献

参考文献5

  • 1Enslin J H R,P J M Heskes.Harmonic Interaction Bet- ween a Large Number of Distributed Power Inverters and the Distribution Network[J].IEEE Trans. on Power Electronics, 2004, 19 (6) : 1586-1593.
  • 2Sun J.Impedance-based Stability Criterion for Grid-conn- ected Inverters[J].IEEE Trans. on Power Electronics, 2011,26 ( 11 ) : 3075-3078.
  • 3许德志,汪飞,毛华龙,阮毅,张巍.多并网逆变器与电网的谐波交互建模与分析[J].中国电机工程学报,2013,33(12):64-71. 被引量:142
  • 4Xu D, Output Impedance Modeling of Grid-connected In- verters Considering Nonlinear Effects[A].In 2012 IEEE 13th Workshop on Control and Modeling for Power Ele- ctronics[C].2012 : 1-7.
  • 5胡伟,孙建军,马谦,刘飞,查晓明.多逆变器并网系统谐振特性分析[J].电力自动化设备,2014,34(7):93-98. 被引量:39

二级参考文献39

  • 1Mohamed Y A-R I. Mitigation of converter-grid resonance, grid-induced distortion, and parametric instabilities in converter-based distributed generation[J]. IEEE Transactions on Power Electronics, 2011, 26(3): 983-996.
  • 2Zeng Q R, Chang L C. An advanced SVPWM-based predictive current controller for three-phase inverters in distributed generation systems[J]. IEEE Transactions on Industrial Electronics, 2008, 55(3): 1235-1246.
  • 3Huerta J M E, Castello-Moreno J, Fischer J R, et al. A Synchronous Reference Frame Robust Predictive Current Control for Three-Phase Grid-Connected Inverters[J].IEEE Transactions on Industrial Electronics, 2010, 57(3): 954-962.
  • 4Massing J R, Stefanello M, Grtlndling H A, et al. Adaptive current control for grid-connected converters with LCL filter[J]. IEEE Transactions on Industri'al Electronics, 2012, 59(11): 4681-4693.
  • 5Liserre M, Teodorescu R, Blaabjerg F. Stability of ph0tovoltaic and wind turbine grid-connected inverters for a large set of grid impedance values[J]. IEEE Transactions on PowerElectronics, 2006, 21(1): 263-272.
  • 6Agorreta J L, Borrega M, Lopez J, et al. Modeling and control of N-paralleled grid-connected inverters with LCL filter coupled due to grid impedance in PV plants[J]. IEEE Transactions on Power Electronics, 2011,26(3): 770-785.
  • 7Enslin J H R, Heskes P J M. Harmonic interaction between a large number of distributed power inverters and the distribution network[J]. Transactions on Power Electronics, 2004, 19(6): 1586-1593.
  • 8Cspedes M, Sun J. Renewable energy systems instability involving grid-parallel inverters[C]//Applied Power Electronics Conference and Exposition. Washington: IEEE, 2009: 1971-1977.
  • 9Chen X, Sun J. A study of renewable energy system harmonic resonance based on a DG test:bed[C]//Applied Power Electronics Conference and Exposition. Texas: IEEE, 2011: 995-1002.
  • 10Sun J . Impedance-based stability criterion for grid-connected inverters[J]. IEEE Transactions on Power Electronics, 2011, 26(11): 3075-3078.