摘要 为深入了解某图书馆阅览室金属微孔顶板辐射空调系统的能耗及室内空气品质情况,通过对该空调控制系统终端运行数据进行采集,得出该空调系统冬、夏工况下的空调运行负荷及阅览室CO_2浓度,并进行了计算与经济分析。结果表明,该空调系统实际运行相对传统空调系统节能,投资回收期为9年。测试发现阅览室空气品质没有达到设计标准,CO_2浓度总体基本维持在720ppm^860ppm之间,分析是新风量不足所导致,提出了相应的改善措施。 To investigate the energy consumption of the micro-porous metal roof radiation air conditioning system operation and indoor air quality in a library reading room, the concentration of CO2 in the reading room was acquired through test experiment and the air conditioning operation load in winter and summer conditions was calculated. Then, by studying on energy saving of this system and economic analysis, it came to the conclusion that the air conditioning system provides superior performance on energy saving compared with traditional air-conditioning and its investment payback period is 9 years. Test indicated that the CO2 concentration in the reading room remained a high level a high level from 721) ppm to 860 ppm which was not up to standard for lacking of fresh air. Relevant measures were proposed to improve such conditions.
出处 《建筑热能通风空调》 2015年第6期5-7,14,共4页 Building Energy & Environment
基金 湖南省自然科学基金项目(13JJ9015)
关键词 金属微孔顶板辐射空调系统 经济性 空气品质 the micro-porous metal roof radiation air conditioning system, energy consumption, indoor air quality
  • 相关文献

参考文献3

二级参考文献58

  • 1龚光彩,周敏锐,徐春雯.薄型低温地暖板采暖舒适性及节能性实测分析[J].湖南大学学报(自然科学版),2009,36(S2):156-160. 被引量:7
  • 2郁文红,杨昭.辐射冷却技术与住宅空调[J].节能,2005,24(6):42-44. 被引量:3
  • 3刘学来 薛红香 李永安 等.毛细管平面辐射空调房间室内计算温度研究.煤气与热力,2010,30(3):24-28.
  • 4刘学来,李永安.毛细管平面辐射空调传热特性的研究[C]//山东,2011年全国冷冻冷藏行业与山东制冷空调行业年会暨绿色低碳新技术研讨会,2011.
  • 5FEUSTEL H E,STETIU C. H ydronic radiant cooling-prelimi- nary assessment[J]. Energy and Buildings, 1995,22(3) : 193 - 205.
  • 6IMANARI T,OMORI T, BOGAKI K. Thermal comfort and energy consumption of the radiant ceiling panel system, com- parison with the conventional all-air system[J]. Energy and Buildings, 1999,30(2) :167-175.
  • 7KILKIS L B, SAGER S S, ULUDAG M. A simplified model for radiant heating and cooling panels[J]. Simulation Practice and Theory, I994,2(2): 61-76.
  • 8ARDEHALI M M, PANAH N G, SMITH T F,et al. Proof of concept modeling of energy transfer mechanisms for radiant conditioning panels[J]. Energy Convection and Management, 2004,45(13/14) : 2005-2017.
  • 9KARADAG Refer. New approach revelant to total heat trans- fer coefficient including the effect of radiation and convection at the ceiling in a cooled ceiling r0om[J]. Applied Thermal Engi- neering, 2009,29 (8) .. 1561 - 1565.
  • 10MIRIEL J, SERRES L, TROMBE A. Radiant ceiling panel heating-cooling systems: experimental and simulated study of the performances, thermal comfort and energy consumptions [J]. Applied Thermal Engineering, 2002, 22 (16) : 1861 - 1873.