期刊文献+

一起数字化变电站主变压器差动保护误动分析

Analysis of a differential protection malfunction of main transformer in digital substation
在线阅读 下载PDF
导出
摘要 针对一起某110kV数字化变电站主变压器差动保护误动作事故进行了深入分析。根据故障录波数据,通过相关技术人员的现场查找和分析,确定了主变压器差动保护误动的原因,即投电容器时,一次系统产生较大的干扰信号,对主变压器低压侧采样系统产生影响,主变压器低压侧各模拟量通道同时产生较大的向下的尖波,导致主变压器差动保护差流瞬时增大,造成比率差动保护动作。根据现场实际情况和误动原因,提出了相关解决方案,并经过了现场实际验证,为类似事故的预防、解决提供了参考。 This paper makes an in-depth analysis of a differential protection malfunction of main transformer in a110 kV digital substation.The cause is found out through on-site examination and analysis of fault recording data by relevant technical personnel.A large interference signal produced by capacitor switching impact the sampling circuit of the low voltage of main transformer.It lead to large downward sharp wave in all the analog channels of secondary sampling circuit of low voltage side of main transformer at the same time,and resulted in an instantaneous increase of the differential current of differential protection malfunction of main transformer,which caused ratio differential protection malfunction of main transformer.According to on-site actual conditions and the malfunction causes,the related solutions are proposed and verified on-site,which provides experience to prevent recurrence of similar incidents in the future.
出处 《供用电》 2015年第11期38-42,共5页 Distribution & Utilization
关键词 数字化变电站 变压器 差动保护 误动 干扰 digital substation transformer differential protection malfunction interference
  • 相关文献

参考文献6

二级参考文献40

  • 1汤汉松,孙志杰,徐大可.数字化变电站的现状与未来[J].江苏电机工程,2007,26(z1):5-7. 被引量:19
  • 2高翔,刘韶俊.继电保护状态检修及实施探讨[J].继电器,2005,33(20):23-27. 被引量:62
  • 3Chatrefou D,Montillet G F.A series of implementation of optical sensors in high voltage substations[C].IEEE PES T&D,2003.
  • 4IEC.IEC 61850:Communication networks and systems in substations[S].2004.
  • 5Anderson L,Brunner C.Substation automation based on IEC 61850with new process-close technology[C].IEEE PowerTech Conference,Bologna,Italy,2003.
  • 6NxtPHASE.Arizona public service-case study[DB/OL].http://www.nxtphase.com,2006,1.
  • 7NxtPhase.NxtPhase optical sensors measurement stability over time andtemperature[DB/OL].http://www.nxtphase.com,2006,1.
  • 8Sanders G A,Blake J N,Rose A H,et al.Commercialization of fiber-optic current and voltage sensors at NxtPhase[C].Optical Fiber Sensors Conference Technical Digest,2002.
  • 9Skeie T,Johannessen S,Brunner C.Ethernet in substation automation[J].IEEE Control Systems Magazine,2002,22(3):43-51.
  • 10Frances Cleveland,Xan thus Consulting International.IEC TC57:Security standards for the power system's information infrastructure -beyond simple encryption[S].2005.

共引文献513

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部