期刊文献+

分布式电源与电网同步的研究 被引量:2

Distributed power supply and power grid synchronization of research
在线阅读 下载PDF
导出
摘要 在分布式电源并网系统中,通过获取电网侧的瞬时相位信息,使逆变器输出与电网保持同频、同相。文章分析了单同步坐标系软件锁相环算法和双二阶广义积分器锁相环算法的性能特点,根据优势互补的方法,通过检测电路检测三相电路的状态,正确地对锁相环进行切换,以快速精确的检测出正序电压和相位,保证系统中的逆变器正常工作。同时通过利用单纯形法对其锁相环的控制器参数进行优化。研究结果表明,根据电网侧的工作状态,合理地切换锁相环的工作模式,可以快速精确地追踪电网相位和频率信息。 Distributed power system obtains the instantaneous phase information of the grid, and controls its inverter output matching the frequency and phase of the grid. The characteristics of SSRF SPLL and DSOGI- SPLL performance are analyzed in this paper. According to the complementary advantages principle, a proper phase-locked loop(PLL) is switched for quick and accurate detection of the positive sequence voltage and phase to implement the normal working of converter based on detected three-phase circuit state. At the same time, the simplex method is used to optimize the PLL controller parameters. The research results show that reasonable switch of the PLL operation mode can track grid phase and frequency information quickly and accurately according to the working state of the grid.
出处 《可再生能源》 CAS 北大核心 2015年第5期725-730,共6页 Renewable Energy Resources
关键词 分布式电源 逆变器 单同步坐标系软件锁相环 双二阶广义积分器锁相环 单纯形法 distributed power inverter SSRF-SPLL DSOGI-SPLL simplex method
  • 相关文献

参考文献3

二级参考文献24

  • 1Zhan Changjiang, Fitzer C, Ramachandaramurthy V K, et al. SoRware phase-locked loop applied to dynamic voltage restorer (DVR) [C]. // Proc. IEEE Power Eng Soc Winter Meeting, 1033-1038.
  • 2Chung Se-kyo. A phase tracking system for three phase utility interface inverters[J]. IEEE Transactions on Power Electronics, 2000, 15 (3): 431-438.
  • 3Hilmy Awad, Jan Svensson, Bollen M J. Tuning software phase-locked loop for series-connected converters[J]. IEEE Transactions on Power Delivery, 2005, 20 ( 1 ): 300-308.
  • 4Karimi-Ghartemani M, Iravani M R. A method for synchronization of power electronic converters in polluted and variable-frequency environments[J]. IEEE Trans onPower Systems, 2004, 19: 1263-1270.
  • 5Ghosh A, Joshi A. A new algorithm for the generation of reference voltages of a DVR using the method of instantaneous symmetrical components[J]. IEEE Power EngRev, 2002, 22 (1): 63-65.
  • 6Rodriguez P, LunaA, Ciobotaru M, et al. Advanced gid synchronization system for power converters under unbalanced and distorted operating conditions[C].//Proc of the 32st Annual Conference of the IEEE Industrial Electronics Society, IECON, 2006: 5173-5178.
  • 7Pedro Rodriguze, Josep Pou Joan Bergas. Decoupled double synchronous reference frame PLL for power converters control[J]. IEEE Transactions on Power Electronics, 2000, 22 (2): 584-592.
  • 8Rodriguez P, Pou J. Double synchronous reference frame PLL for power converters[C] // Proc IEEE Power Electron Spec Conf, 2005: 1415-1421.
  • 9Karimi-Ghartemani M, Iravani M R. A method for synchronization of power electronic converters in polluted and variable-frequency environments[J]. IEEE Trans on Power Systems, 2004, 19(1): 1263-1270.
  • 10Chung S K. Phase-locked loop for grid-connected three-phase power conversion systems[J]. Electric Power Application, IEEE Proceedings, 2000, 147(3): 213-219.

共引文献101

同被引文献13

引证文献2

二级引证文献19

相关作者