期刊文献+

医院病房人流量特征及新风量需求 被引量:3

Characteristics of traffic flow and outdoor air requirement in hospital wards
在线阅读 下载PDF
导出
摘要 提出了影响病房新风量的两个特征参数——人员数量和人员在室停留时间,结合调研数据,给出了不同科室的人员数量及停留时间特征。提出了抗冲击能力强度与抗冲击时间两个新风供应能力参数,建立了基于此参数的病房新风调控判据。根据算例分析,认为病房新风设计换气次数值宜大于2h-1,并提出了调控策略。 Puts forward the two characteristic parameters which influence outdoor air supply of hospital wards, i.e. the number of occupants and the indoor residence time of person. Combining with the survey data, provides the characteristics for the number of occupants and the residence time in different departments. Gives the two outdoor air supply parameters, i.e. impact resistance strength and impact resistance time. Establishes the outdoor air control criterion on the basis of the parameters. According to the analysis of the case, considers that the outdoor air change rate for outdoor air design of the wards should be greater than 2 h-1. And presents the corresponding control strategy.
作者 居发礼
出处 《暖通空调》 北大核心 2015年第4期25-28,100,共5页 Heating Ventilating & Air Conditioning
关键词 病房 人员数量 新风量 室内环境 室内CO2浓度 ward, number Of occupant, outdoor air volume, indoor environment, indoor CO2 concentration
  • 相关文献

参考文献4

  • 1王刚,张婕,秦海波.医院门诊及病房日间人员流量分析[J].中国医院统计,2007,14(3):244-246. 被引量:5
  • 2上海市民用建筑设计院.JGJ 49—1988综合医院建筑设计规范[S].北京:中国建筑工业出版社,1989.
  • 3中国建筑科学研究院.GB50736-2012民用建筑供暖通风与空气调节设计规范[s].北京:中国建筑工业出版社,2012.
  • 4刘宇.基于CO2浓度的医院病房新风量需求分析[J].建筑热能通风空调,2011,30(增刊):169-171.

二级参考文献9