期刊文献+

多联机与新风机复合空调系统优化控制研究 被引量:10

Investigation on Optimal Control of Hybrid Air Conditioning System with Multi-split Air Conditioner and Fresh Air Unit
在线阅读 下载PDF
导出
摘要 尽管变制冷剂流量(VRF)多联机系统在部分负荷工况下具有高能效的显著优点,但是该系统仍然存在缺少新风的缺点。本文提出了一种多联机与新风机复合空调系统降低能耗的优化控制策略。在建立的系统仿真模型基础上,本文以一办公楼为例,对提出的优化控制策略进行了制热工况下的仿真研究。结果表明,提出的优化控制策略是可行的,可以有效地降低复合空调系统的能耗。 Although variable refrigerant flow (VRF) multi-split air conditioner systems have good energy performances in part load conditions, the shortcoming of no outdoor air intake has not been solved thoroughly. An optimal control strategy for combined air conditioning system (with VRF unit and outdoor air processing unit) aiming at reducing energy consumption is presented in this paper. Based on the developed simulation platform, the proposed optimal control strategy is evaluated in heating mode. Results show that the proposed optimal control is feasible, which can effectively decrease the energy consumption of the combined system.
出处 《制冷技术》 2015年第1期6-10,共5页 Chinese Journal of Refrigeration Technology
关键词 复合空调系统 变制冷剂流量 新风机 优化控制 Combined air conditioning system Variable refiigerant flow Outdoor air processing unit Optimal control
  • 相关文献

参考文献13

  • 1刘传聚,郑文.多联式空调(热泵)机组性能及应用述评[J].制冷技术,2006,26(4):7-11. 被引量:19
  • 2周鹏飞,贺群妮.多联机空调系统运行性能的影响因素分析[J].制冷技术,2012,32(3):62-65. 被引量:16
  • 3薛卫华,沈建芳,苏志军,陈沛霖,刘传聚.VRV空调系统与螺杆式风冷热泵空调系统全年能耗比较[J].制冷技术,2003,23(4):6-9. 被引量:13
  • 4LIU X B, HONG T Z. Comparison of energy efficiency between variable refrigerant flow systems and ground source heat pump systems[J]. Energy and Buildings, 2010, 42(5): 584-589.
  • 5KARUNAKARAN R, INIYAN S, RANKO G Energy efficient fuzzy based combined variable refrigerant volume and variable air volume air conditioning system for buildings[J]. Applied Energy, 2010, 87(4): 1158-1175.
  • 6PARAMESHWARAN R, KARUNAKARAN R, VINU R, et al. Energy conservative building air conditioning system controlled and optimized using fuzzy-genetic algorithra[J]. Energy and Buildings, 2010, 42(5): 745- 762.
  • 7ZHU Y H, JINX Q, DU Z M, et al. Generic simulation model of multi-evaporator variable refrigerant flow air conditioning system for control analysis[J]. International Journal of Refrigeration, 2013, 36(6): 1602-1615.
  • 8ZHU Y H, JIN X Q, DU Z M, et al. Simulation of variable refrigerant flow air conditioning system inheating mode combined with outdoor air processing unit[J]. Energy and Buildings, 2014, 68(1): 571-579.
  • 9ZHU Y H, JINX Q, DU Z M, et al. Control and energy simulation of variable refrigerant flow air conditioning system combined with outdoor air processing unit[J]. Applied Thermal Engineering, 2014, 64(1/2): 385-395.
  • 10WANG S W, J1N X Q. CO2-based occupancy detection for on-line outdoor air flow control[J]. Indoor and Built Environment, 1998, 7(3): 165-181.