大连某海水源热泵区域供热系统的实测分析 被引量:4

Field measurement and analysis of a seawater source heat pump district heating system in Dalian
在线阅读 下载PDF
导出
摘要 根据现场实测数据,分析了热泵机组及整个热泵区域供热系统的能效情况。结果表明,海水源热泵机组在冬季海水温度极低的情况下仍可运转,但机组的制热性能系数很低(约为2.43),系统整体的制热性能系数则更低(测试平均值为1.86)。进一步分析了影响机组制热性能的因素。模拟计算发现,若选择市场上性能优良的热泵机组,其制热性能系数将提升34.2%,系统整体能效可提升约24.2%。 Based on the field measurement data, analyses the energy efficiency values of the seawater source heat pump unit and the whole district heating system. The results show that the seawater source heat pump unit can still run under very low seawater temperature condition in winter, but the coefficient of heating performance (COP) of the unit is quite low (as low as 2.43) and the COP of the whole system is even lower (with an average of 1.86). Then analyses the influencing factors on the heating performance of the heat pump unit. Simulation result shows that the heating COP of the heat pump unit can increase 34. 2%, and the heating COP of the system can increase 24.2% just by the substitution of the current seawater source heat pump unit with better performance ones in the market.
出处 《暖通空调》 北大核心 2014年第11期62-66,74,共6页 Heating Ventilating & Air Conditioning
基金 "十二五"国家科技支撑计划项目(编号:2014BAJ01B04)
关键词 海水源热泵 热泵机组 区域供热 实测 制热性能系数 seawater source heat pump, heat pump unit, district heating, field measurement, coefficient of heating performance