期刊文献+

三相四桥臂逆变器的分序前馈解耦控制的研究

Research on Decomposition Sequence and Feedforward Decoupling Control of Three-phase Four-leg Inverter
在线阅读 下载PDF
导出
摘要 三相三桥臂逆变器一般给三相对称负载供电,针对不对称负载和非线性负载,我们一般采用三相四桥臂逆变器.采用对称向量法,将三相输出电压和电感电流分解正序分量,负序分量和零序分量,在正序dq坐标系(零序分量在正序dq坐标系下)和负序dq坐标系进行旋转变换,采用前馈解耦对系统进行解耦,在三个dq坐标系下对正序分量,负序分量和零序分量进行独立控制.在matlab/simulink平台下进行仿真,仿真结果证明上述所提方法的正确性,并且优于传统的单同步旋转双闭环控制策略. Three-phase three-leg inverters generally supplies power to the three-phase symmetric loads. For asymmetric and nonlinear loads, we generally use three-phase four-leg inverter. A symmetric vector method adopted in this paper decomposes three-phase output voltage and inductor current into positive, negative and zero sequence component. Then it makes rotating change in the d-q coordinate system of positive and negative sequence. (The zero-sequence component is under positive sequence coordinates). The forward-feed decouple method adopted is to decouple the control system, and independently regulates the positive, negative and zero sequence component in three d-q coordinate system. It is carried out in matlab / simulink platform simulation and the results prove the correctness of the methods mentioned above. This method is superior to the traditional single svnchronous rotation douhle-loon control strategy.
出处 《湖南工程学院学报(自然科学版)》 2014年第3期5-9,共5页 Journal of Hunan Institute of Engineering(Natural Science Edition)
关键词 逆变器 对称分量法 三相四桥 inverter method of symmetrical components three-phase three-leg
  • 相关文献

参考文献8

二级参考文献20

  • 1孙驰,鲁军勇,马伟明.一种新的三相四桥臂逆变器控制方法[J].电工技术学报,2007,22(2):57-63. 被引量:33
  • 2Yao Guijun,Phillips S, Norum L. Three-phase inverters analysis of ability to maintain symmetrical output voltage [C]//IECON' 1993. Denvor, Colorado, USA, 1993: 1033-1038.
  • 3Venkataramanan G, Divan D M, lahns T M. Discrete pulse modulation strategies for high-frequency inverter systems[J]. IEEE Trans on PE, 1993,8(3): 279-287.
  • 4Zhang R, BoroyevichD,PrasadVH, et al. A three-phase inverter with a neutral leg with space vector modulation [C]//IEEEAPEC' 97. Atlanta, Georgia, USA, 1997: 57-863.
  • 5Ryan M J, De Doncker R W, Lorenz R D. Decoupled control of a four-leg inverter via a new 4 × 4 transformation matrix[J]. IEEE Trans on PE,2001,16(5) :694-700.
  • 6Quinn C A, Mohan N, Mehta H. A four-wire current controlled converter provides harmonic neutralization in threephase four wire systems[C]//IEEE APEC'93. San Diego, California, USA, 1993 : 841 - 846.
  • 7Hsu P, Behnke M. A three-phase synchronous frame controller for unbalanced load[C]//IEEE PESC'98. Fukuoka, Japan, 1998: 1369-1374.
  • 8Fortescue C L. Method of symmetrical coordinates applied to the solution of polyphase networks[J]. The 34th Annual Convention of the American Institute of Electrical Engineering. Atlantic City, NJ, 1918:1027-- 1140.
  • 9Choi J H, Kwon J M,Jung J H, et al. High-performance online UPS using three-leg-type converter[J]. IEEE Transactions on Industrial Electronics, 2005,52(3) : 889-897.
  • 10林金燕,王正仕,陈辉明,李超.一种高性能三相四桥臂逆变器控制器的设计[J].中国电机工程学报,2007,27(22):101-105. 被引量:31

共引文献102