摘要
分析大型发电厂6kV封闭母线在停运后绝缘值下降的原因,提出一种简便、高效、可靠的提高母线绝缘值的方法,即在绝缘子表面喷涂RTV。该方法经实际应用效果良好,母线绝缘值有很大提高,提出了从根本上解决封闭母线绝缘低的处理对策。
This paper analyses the reason why insulation of6kV enclosed bus bar becomes bad when it is not in operation,A sim-ple,effective,reliable method for solving this problem is to spray RTV on the surface of the insulators of the bus bar.The method has good effort in application,and the insulation of the bus bar has been greatly improved.