摘要 论述了电网谐波分析与滤除系统的结构、原理和功能 ,阐述了谐波的检测与分析、系统控制信号的计算与产生 .系统主电路是 1个混合有源滤波器 ,系统软件包括基波及各次谐波的检测、统计分析、历史数据查询和报警等模块 .系统采用快速傅里叶变换进行谐波分析 ,并提出一种改进规则采样法对混合有源滤波器进行谐波跟踪控制 .实验结果表明 ,系统对各电量的检测误差均小于 2 % ,三相电压总畸变率由滤波前的 10 .5 % ,11.3%和 11.7%下降到滤波后的 3.9% ,4.2 %和 4.4% ,三相电流总畸变率由滤波前的 2 6 .2 % ,2 5 .7%和 2 5 .8%下降到滤波后的 7.9% ,6 .9%和 7.4% . A harmonic analysis and elimination system is proposed in this article. The harmonic analysis software and a hybrid active power filter with improved regular sampling method are described. The experimental results show that the detection error is less than 2%, the THDs of voltage of three phases have been reduced to 3.9%, 4.2% and 4.4% from 10.5%, 11.3% and 11.7% respectively, and that the THDs of voltage of three phases have been reduced to 7.9%, 6.9% and 7.4% from 26.2%, 25.7% and 25.8% respectively.
作者 罗安 涂春鸣
出处 《中南工业大学学报》 CSCD 北大核心 2001年第6期631-634,共4页 Journal of Central South University of Technology(Natural Science)
基金 国家计委自动化高技术项目 (计投资 [2 0 0 0 ] 2 498号 )
关键词 谐波分析 谐波滤除 混合有源滤波器 电网 非线性负载 畸变率 harmonic analysis harmonic elimination hybrid active power filter improved regular sampling method
  • 相关文献

参考文献7

  • 1黄俊.电力电子变流技术(第3版)[M].北京:机械工业出版社,1993..
  • 2林干,何志华,李正国,罗安,邓路明.智能型电网谐波监视分析及保护一体化装置[J].电力系统自动化,2000,24(1):64-66. 被引量:39
  • 3王兆安 杨君 等.谐波抑制与无功功率补偿[M].北京:机械工业出版社,1999..
  • 4王兆安,谐波抑制与无功功率补偿,1999年
  • 5黄俊,电力电子变流技术(第3版),1993年
  • 6Peng F Z,IEEE Transaction on Industrial Applications,1990年,26卷,6期,983页
  • 7吴竟昌,电力系统谐波,1988年

二级参考文献3

  • 1曹孝宁,吴华仁,李晓惠,龙可微.高性能电网谐波分析仪[J].电力系统自动化,1996,20(12):46-49. 被引量:14
  • 2阿基累斯D 史习智(译).信号处理中的傅立叶变换[M].北京:科学出版社,1991..
  • 3史习智,信号处理中的傅立叶变换,1991年

共引文献45

同被引文献90

引证文献12

二级引证文献271

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部