和应涌流对变压器差动保护影响的试验研究 被引量:39

Test and study on the effect of surge current on differential protection for transformer
在线阅读 下载PDF
导出
摘要 大坝发电厂 1号发变组差动保护 ,在 2号主变反送电空投时往往引起误动作。为此 ,作了 2号主变反送空投试验 ,试验发现 :空投 2号主变时 ,在 1号主变中产生和应涌流 ,分析研究了和应涌流对变压器差动保护的影响 ,得出了和应涌流是变压器差动保护误动的原因之一的结论。并提出了变压器差动保护防止和应涌流误动的技术措施。 For the differential protection for #1 generator-transformer set in Daba power plant, it has maloperations several times as #2 main transformer operating without load during power inverse transmission. Therefore, a test on #2 main transformer in such conditions is done and it is found that when the #2 main transformer operating without load, a surge current is produced in #1main transformer. After analyzing the effect of the surge current on the differential protection for transformer, it shows that the surge current is something to bring the maloperation of the differential protection for transformer. Thus the solutions to above problems are proposed.
机构地区 宁夏大坝发电厂
出处 《继电器》 CSCD 北大核心 2001年第7期52-54,共3页 Relay
关键词 和应涌流 变压器 差动保护 试验 继电保护 电网 surge current transformer differential protection test study
  • 相关文献

参考文献2

  • 1王维俭 候炳蕴.大型机组断电保护理论基础[M].北京:中国电力出版社,1996..
  • 2王怀智.大坝发电厂1号机组大差保护误动原因的分析研究.第六届全国继电保护学术研讨会论文集[M].深圳:中国电机工程学会继电保护专业委员会,1996..