期刊文献+

基于Matlab/Simulink的直流输电系统异常引起的发电机组失步保护动作仿真分析 被引量:4

Matlab/Simulink Based Simulation Analysis of Generator Out-of-step Protection Action Caused by DC Transmission System Abnormalities
在线阅读 下载PDF
导出
摘要 某直流输电工程站间无通信情况下逆变站手动紧急停运试验时,逆变侧紧急停运后,整流站没有及时闭锁,引起整流侧交流系统振荡,导致某电厂发电机组失步保护动作于停机。基于事故期间的PMU装置采集到的发电机组机端电流、电压的幅值和相角,根据失步发电机参数进行三阻抗元件失步保护整定计算,利用Matlah/Sinmulnk成功再现了事故发生时发电机机端测量阻抗顺序穿越三阻抗元件动作区域的全过程,根据仿真结果分析了发电机失步原因,提出了合理的改进措施。 The inverter station manual emergency shutdown test of a DC transmission project was conducted under the condition of no communication between the rectification and inverter station.When the inverter station blocked,rectification station did not block immediately,which cause the AC system oscillation on the rectification station side,leading to a power plant's unit out-of-step protection action to stop.Based on the generator's amplitude and phase angle of current and voltage collected by the PMU device during the accidents,three impedance element out-of-step protection setting calculation is made according to the parameters of the out-of-step generator.Matlab / Simulink software is used to represent the measure impedance of generator sequence through the action area of three impedance components in the order process.The out-of-step reasons of the generator are analyzed,reasonable improvement measures are put forward according to the simulation results.
出处 《陕西电力》 2014年第2期70-73,共4页 Shanxi Electric Power
关键词 直流故障 失步保护 PMU 振荡 仿真 DC transmission system abnormalities out-of-step protection PMU system oscillation simulation
  • 相关文献

参考文献10

二级参考文献71

共引文献118

同被引文献33

引证文献4

二级引证文献23

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部