期刊文献+

船舶中压电网消弧线圈接地方式机理研究 被引量:2

Mechanism study of resonant neutral grounding scheme for shipboard medium voltage power grid
在线阅读 下载PDF
导出
摘要 消弧线圈接地方式用于船舶中压电网时,对其机理和规律迄今还缺乏定量研究。在对船舶中压电网单相接地故障进行理论分析的基础上,结合暂态仿真,研究了消弧线圈阻尼率、脱谐度以及发电机频率偏移、燃弧时刻角等对熄弧恢复电压、重燃过电压、中性点位移电压以及故障电流的影响。结果表明,增大阻尼率将减小熄弧电压恢复超调量,从而降低重燃过电压,但也会使故障电流有所增加;而增加脱谐度会使得熄弧电压恢复超调量增加,可能引起较大的重燃过电压,为了限制故障电流,脱谐度不宜取值过大;此外,发电机频率偏移也可能导致较大的暂态过电压。 At present, a quantitative research on the mechanisms and laws of the application of resonant neutral grounding (RNG) to shipboard medium voltage (MV) power grid is scarce. Based on the theoretical analysis of single-phase to ground fault for shipboard MV power grid, combining with transient simulation, the paper studies the impact of damping ratio and tuning degree of arc-suppression coil on arc-extinct recovery voltage, re-strike overvoltage, neutral displacement voltage and fault current. The effects of generator frequency offset and arc angle are also discussed. The results show that increasing the damping ratio will decrease the arc-extinct voltage recovery overshoot, thereby reducing re-strike overvoltage, but will also increase fault current. While increasing tuning degree will increase the arc-extinct voltage recovery overshoot, and possibly cause greater re-strike overvoltage, so the tuning degree should be appropriate to restrict the fault current. In addition, the generator frequency offsets can also lead to greater transient overvoltage.
出处 《电力系统保护与控制》 EI CSCD 北大核心 2013年第23期23-29,共7页 Power System Protection and Control
关键词 船舶中压电网 消弧线圈接地 熄弧恢复电压 重燃过电压 故障电流 shipboard medium voltage (MV) power grid resonant neutral grounding (RNG) arc-extinct recovery voltage re-strike overvoltage fault current
  • 相关文献

参考文献7

二级参考文献80

共引文献227

同被引文献8

引证文献2

二级引证文献8

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部