期刊文献+

配网励磁涌流导致保护误动原因分析与抑制方法研究 被引量:13

Analysis and Restraining Method of Protection Malfunction Caused by Distribution Network Magnetizing Inrush Current
在线阅读 下载PDF
导出
摘要 由于配网线路装有大量的配电变压器,在线路投运合闸瞬间,各变压器所产生的励磁涌流在线路上相互叠加,来回反射,产生了一个复杂的电磁暂态过程,在系统阻抗较小时,会出现较大的涌流,时间常数也较大,造成线路投运瞬间电流速断保护误动。笔者针对这类跳闸事故进行研究,对发生励磁涌流跳闸时的相关数据和录波波形进行分析研究,开发了一种基于数字陷波器的波形处理算法,对保护软件进行改进,实现抑制配电网励磁涌流跳闸的目的。且经过试验验证,证明该方法可以有效地抑制涌流跳闸事故。 Because of distribution network are fitted with plenty of distribution transformers, switch instant, all magnetizing inrush current of transformers are superposition to form a complicated magnetic transient process. On the time of system resistance reduced and time constant increased, magnetizing inrush current will become a larger to cause protection malfunction. The related data and recorded waveforms in magnetizing inrush current tripping are introduced in this paper. For interference suppression of magnetizing inrush current, a new method which is based on a notch filter is presented. The test results show that the method above-mentioned can suppress the inrush current triooing accidents effectively.
作者 任明辉
机构地区 宝鸡供电局
出处 《高压电器》 CAS CSCD 北大核心 2013年第12期59-63,68,共6页 High Voltage Apparatus
关键词 励磁涌流 二次谐波 电流速断保护 数字陷波器 magnetizing inrush current second harmonic current quick-break protection digital notch filter
  • 相关文献

参考文献12

二级参考文献86

共引文献584

同被引文献148

引证文献13

二级引证文献119