数据机房自然冷却用泵驱动回路热管换热机组性能实验研究 被引量:24

Experimental Analysis on Function of Free Cooling Unit with a Pump-driven Loop Heat Pipe for Internet Data Center
在线阅读 下载PDF
导出
摘要 设计了一种数据中心自然冷却用泵驱动回路热管换热机组,并介绍该机组的构成和工作原理,针对研制的样机搭建实验系统并较全面地进行实验研究。结果表明:当室内外温差为10℃时,机组能效比COP为5.88;当室内外温差为18℃时,机组COP可达10.41;当系统质量流量在一定范围变化时,即工质气化率在2%~50%范围内,机组换热量没有显著变化,且换热量与室内外温差近似呈线性关系;同时系统阻力越大,蒸发器进出口温差越大,显热换热量所占比例也越大。 A free cooling unit with a pump-driven loop heat pipe was designed for internet data center(IDC),and its components and working processes were described.The experiment system for the developed prototype was built and the comprehensive studies were conducted.The experimental results demonstrate that the coefficient of performance(COP) of the unit can reach to 5.88 when the temperature difference between IDC indoor and outdoor is 10℃,and it will be 10.41 when the temperature difference is 18℃.When mass flow rate of the working fluid in the unit changes within a certain range,namely the gasification rate of the fluid being between 2% and 50%,there is no significant changes for the heat transfer capacity.And there is an approximately linear relationship between the capacity and the temperature difference.Meanwhile,with the increase of the system resistance,both temperature difference of the fluid between inlet and outlet of the evaporator and the proportion of the sensible heat to the capacity also increase.
出处 《土木建筑与环境工程》 CSCD 北大核心 2013年第4期145-150,共6页 Journal of Civil,Architectural & Environment Engineering
基金 国家自然科学基金(51076003)
关键词 数据中心节能 回路热管 自然冷却 energy efficiency for internet data center loop heat pipe free cooling
  • 相关文献

参考文献21

  • 1云计算发展与政策论坛委员会.数据中心能效测评指南(V1.0)[R].北京.云计算发展与政策论坛,2012.
  • 2ASHRAE TC 9. 9.数据通信设施节能最佳实践[M].任兵,杨国荣,陈亮.译.北京:中国建筑工业出版社,2010.
  • 3钱晓栋,李震.数据中心空调系统节能研究[J].暖通空调,2012,42(3):91-96. 被引量:122
  • 4全球最节能数据中心Top 5 [R/OL]. http://tech.sina. com. cn/s/2010-10-15/10294750567. shtml (2012-11-29).
  • 5Jinkyun C, Taisub L, Byungseon S K. Cooling systemsfor IT environment heat removal in (internet) datacenters [J]. Journal of Asian Architecture and BuildingEngineering, 2008,7(2) :387-394.
  • 6Kumar A, Josh I Y. Use of airside economizer for datacenter thermal management [C] //Proceedings of 2ndInternational Conference on Thermal Issues in EmergingTechnologies, Cairo, Egypt,New York: IEEE, 2008:57-66.
  • 7黄成龙,杨文鹏.移动通信基站节能控制的理论与实践[J].西安工程大学学报,2008,22(2):205-209. 被引量:21
  • 8Shehabi A. Energy implications of economizer use inCalifornia data centers [R]. Lawrence BerkeleyNational Laboratory, 2008. http? //escholarship. org/uc/item/4px2n6jn.
  • 9Choi J,Jeon J,Kim Y. Cooling performance of a hybridrefrigeration system designed for telecommunicationequipment rooms [Jl Applied Thermal Engineering,2007,27:2026-2032.
  • 10石文星,韩林俊,王宝龙,周德海,李先庭.热管/蒸气压缩复合空调原理及其在高发热量空间的应用效果分析[J].制冷与空调,2011,11(1):30-36. 被引量:51

二级参考文献68

共引文献273

同被引文献194

引证文献24

二级引证文献137

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部