期刊文献+

基于多同步旋转变换的并联型APF补偿策略 被引量:9

Shunt APF control strategy based on multiple synchronous rotating transform
在线阅读 下载PDF
导出
摘要 为了提高有源电力滤波器(APF)的补偿灵活性,提出基于多同步旋转变换的低次特征谐波选择性补偿策略.采用特定旋转频率的同步旋转变换将相差6次的一对正、负序谐波变换为该坐标系下的3次谐波分量,通过多组不同旋转频率的同步旋转变换将指定谐波变换为相应坐标系下的3次谐波,设计基于谐振控制器、选通频率为150Hz的带通滤波器将其滤出,实现指定谐波的指令提取.为了提高补偿电流的控制精度,采用基于PI控制内环和重复控制外环的复合电流环控制策略.利用MATLAB/SIMULINK软件搭建仿真模型并在16.5kVA的APF样机上进行验证实验,仿真和实验结果证明了该方法在三相并联APF中的正确性和可行性. A novel selective low order harmonic current control strategy was proposed based on multiple synchronous rotating transform in order to improve the compensation flexibility of shunt active power filter (APF). Each couple of harmonics was converted to a pair of 3rd harmonics by a specific synchronous rotating transform. Then the complete low order harmonic current detection can be realized by the superposition of several synchronous rotating transforms with different rotating frequency or rotating direction. A band pass filter of which the selective frequency is three times of the fundamental frequency was designed in order to detect the 3rd harmonics. Equivalent control plant of shunt APF was built. Double-loop control strategy which consists of inner PI control and outer repetitive control was adopted to improve the precision of harmonic current compensation. Simulation model was constructed, and experiment was performed on a 16. 5 kVA rated APF prototype. Simulation and experimental results showed the validity and feasibility of the proposed method.
出处 《浙江大学学报(工学版)》 EI CAS CSCD 北大核心 2013年第4期705-710,共6页 Journal of Zhejiang University:Engineering Science
基金 国家自然科学基金资助项目(51177147) 浙江省重点科技创新团队资助项目(2010R50021)
关键词 有源电力滤波器(APF) 多同步旋转变换 带通滤波器 重复控制 active power filter (APF) multiple synchronous rotating transform band pass filter repetitivecontrol
  • 相关文献

参考文献13

二级参考文献79

共引文献453

同被引文献107

  • 1许树楷,宋强,朱永强,刘文华,李建国.用于不平衡补偿的变压器隔离型链式D-STATCOM的研究[J].中国电机工程学报,2006,26(9):137-143. 被引量:54
  • 2魏学良,戴珂,方昕,康勇.三相并联型有源电力滤波器补偿电流性能分析与改进[J].中国电机工程学报,2007,27(28):113-119. 被引量:68
  • 3HANSON D J, WOODHOUSE M L, HORWIEL C, et al. STATCOM: a new era of reactive compensation[J]. Power Engineering Journal, 2002, 16(3): 151-160.
  • 4EI-HABROUK M, DARWISH M K, MEHTA E Active power filters: a review[J]. IEE Proc-Electr Power Appl, 2000, 147(5): 403-413.
  • 5SOZANSKI K P. Sliding DFT control algorithm for three-phase active power filter[C] // Applied Power Electronics Conference and Exposition, APEC' 06. Twenty-First Annual IEEE, 2006: 1223-1229.
  • 6JACOBSEN E, LYONS R. The sliding DFT[J]. Signal Processing Magazine, IEEE, 2003, 20(2): 74-80,.
  • 7ANNAM'ARIA R, V'ARKONYI-K'OC Z Y. A recursive fast Fourier transformation algorithm[J]. IEEE Trans Circuits Syst II, 1995, 42(9): 614-616.
  • 8PENG F Z,LAI J S,MCKEEVER J,et al. A multilevel voltage- source inverter with separate DC sources for static var generation [J]. IEEE Transactions on Industry Applications,1996,32 (5): 1130-1138.
  • 9BLAZIC B,PAPIC I. Improved D-STATCOM control for operation with unbalanced currents and voltages[J]. IEEE Transactions on Power Delivery,2006,21 (1) :225 -233.
  • 10BARRENA J A,MARROYO L,RODRIGUEZ M A,et al. Individual voltage balancing strategy for PWM cascaded H-bridge converter- based STATCOM[J]. IEEE Transactions on Industrial Electronics, 2008,55( 1 ) :21-29.