运行中500 kV输电线路绝缘子串自然积污及污闪特性研究 被引量:13

Pollution Accumulation and Flashover Performance of Insulator Strings on 500 kV AC Transmission Line Under Service Voltage
在线阅读 下载PDF
导出
摘要 500 kV输电线路是我国电网的主干网架,运行中一旦发生绝缘子污闪事故将严重威胁电力系统可靠运行,因此了解运行电压下绝缘子的自然积污规律及其污闪特性十分重要。对重庆电网某500 kV交流输电线路运行中绝缘子的自然积污情况及污闪特性开展了测试研究,研究结果表明:运行中绝缘子上/下表面累积的盐密/灰密有差异,且下表面的盐密/灰密较上表面的严重;运行中绝缘子表面灰密累积速度大干盐密累积速度;运行中各串绝缘子以及绝缘子串中各片绝缘子的积污均存在差异;自然积污下绝缘子污闪电压比人工染污下绝缘子污闪电压高;污秽成分及绝缘子表面污秽分布的差异是导致运行中绝缘子污闪电压高的主要原因。 500kV transmission line is the backbone of Chinese power grid. The event of insulator pollution flashover under service voltage may serious threat to reliable operation of power systems, so it is important to study the natural characteristic of pollution accumulation and flashover performance of insulator energized the operating voltage. This paper mainly focus on the insulator strings operating in certain 500kV power network in Chongqing, tests and analyzes the pollution depositing rules and flashover performance of them. Test results indicate that the value of equivalent salt deposit density (ESDD) on the top surface of insulator is lower than that on the bottom, as well as the value of non-soluble deposit density (NSDD);the accumulation rate of NSDD is heavier than that of ESDD; the pollution depositing on each insulator string and each insulator are different; at the same pollution level, the flashover voltage of natural contaminated insulator is higher than that of artificial polluted insulator, which mainly caused by the difference of pollution composition and non-uniform pollution distribution on the insulator surface.
出处 《陕西电力》 2013年第4期24-30,共7页 Shanxi Electric Power
关键词 绝缘子 等值盐密 等值灰密 自然积污 闪络电压 insulator ESDD NSDD natural contamination depositing flashover voltage
  • 相关文献

参考文献28

  • 1张开贤.悬式绝缘子串自然积污规律的探讨[J].电网技术,1997,21(3):39-43. 被引量:29
  • 2周建国,肖嵘.多伞盘式绝缘子的污秽特性[C].电工陶瓷第七次学术年会暨学术交流会论文集,2001:77-81.
  • 3蒋兴良,谢述教,舒立春,孙才新,司马文霞.低气压下三种直流绝缘子覆冰闪络特性及其比较[J].中国电机工程学报,2004,24(9):158-162. 被引量:47
  • 4YE H,ZHANG J,JI Y M,et al. Comamination Accumulation and Withstand Voltage Characteristics of Various Types of Insulators [C].Nagoya:Proceedings of the 7th International Conference on Properties and Applications of Dielectric Materials, 2003.
  • 5SUZUKI Y,ITO S,AKIZUKI M,et al. Artificial Contamination Test Method on Accumulated Contamination Conditions[C]. London:The 1 lth International Symposium on High Voltage Engineering, 1999.
  • 6ZEDAN F M, AKABAR M A. Performance of HV Transmission Line Insulators in Desert Conditions. IV. Study of Insulators at A Semicoast Site in the Eastern Region of Saudi Arabia [J]. IEEE Transactions on Power Delivery, 1991,6( 1 ) : 439-447.
  • 7宿志一,刘燕生.我国北方内陆地区线路与变电站用绝缘子的直、交流自然积污试验结果的比较[J].电网技术,2004,28(10):13-17. 被引量:120
  • 8RAMOS N G, CAMPILLO R M T, NAITO K.A Study on the Characteristics of Various Conductive Contaminants Accumulated on High Voltage Insulators [J].IEEE Transactions on Power Delivery, 1993,8(4) : 1842-1850.
  • 9MATSUOKA R, KONDO K. Influence of Non-soluble Contaminants on the Flashover Voltages of Artificially Contaminated Insulators [J].IEEE Transactions on Power Delivery, 1996,11 (1):420-430.
  • 10SUNDARARAJAN R,GORUR R S.Role of Non- soluble Contaminants on the Flashover Voltage of Porcelain Insulators [J].IEEE Transactions on Dielectrics and Electrical Insulation, 1996,3 ( 1 ) : 113-118.

二级参考文献109

共引文献384

同被引文献118

引证文献13

二级引证文献90

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部