风电接入对继电保护的影响(三)——风电场送出变压器保护性能分析 被引量:36

Impact of wind farm integration on relay protection(3): performance analysis for wind farm outgoing transformer protection
在线阅读 下载PDF
导出
摘要 仿真分析发现双馈式风电机组低电压穿越期间的短路电流频率随故障前工况偏移工频。当变压器内部故障时,基于相量值的差动与制动电流将大范围波动,基于采样值的差动保护在某些采样点动作条件不满足,差动保护均无法准确稳定地动作。以某地区实际风电接入为例,在EMTDC平台上对风电场主变压器以及风电集群再升压变压器保护进行离线动作性能测试分析,结果表明,基于相量值及基于采样值的差动保护均无法保证快速动作,风电机组类型、运行工况、故障位置、故障类型及短路容量比是影响风电场送出变压器保护正确动作的因素。 Simulative analysis shows that the short circuit current frequency of doubly-fed induction generator during low-voltage ride-through period deviates from the fundamental frequency according to the working conditions before the fault. When the transformer internal fault occurs,the differential action and braking currents of differential protection based on phasor values fluctuate widely and the action conditions of differential protection based on sample values are not satisfied at certain sampling points ,resulting in the incorrect and instable operations. With an actual regional wind farm as an example,the off-line action performance of the main transformer protection of wind farm and the step-up transformer protection of wind power group is tested and analyzed on EMTDC platform,which shows that,the fast action of differential protection based on either phasor or sample values can not be ensured and the factors influencing the accurate operation of protections for wind farm outgoing transformers are generator type ,operating condition, fault location,fauh type and short circuit capacity ratio.
出处 《电力自动化设备》 EI CSCD 北大核心 2013年第3期1-8,共8页 Electric Power Automation Equipment
基金 国家自然科学基金资助项目(51277143)~~
关键词 低电压穿越 双馈式风电机 风电场 送出变压器 差动保护 继电保护 变压器 low-voltage ride-through doubly-fed induction generator wind farms outgoing transformer differential protection relay protection electric transformers
  • 相关文献

参考文献14

二级参考文献35

共引文献264

同被引文献482

引证文献36

二级引证文献558

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部