期刊文献+

电压互感器铁磁谐振过电压及防止 被引量:33

Ferroresonance Over Voltage on Power Transformer and Its Prevention
在线阅读 下载PDF
导出
摘要 简要分析了TV(电压互感器 )铁磁谐振过电压的机理。综合分析了下列谐振措施 :TV开口三角绕组接电阻或分频谐振装置 ,TV中性点经接地电阻接地或经XXQ 1 0接地 ,在TV中性点串单相TV ,采用抗谐振型电压互感器 ,提出了它们的适用范围。为城网改造 ,新建变电站TV的选型提供参考 。 In the 3~10 kV power supply system,the neutral point of power transformer is grounded.When lightning occurs or no load bus switches on the ferroresonance over voltage,porcelain insulator flashover,lighting arrester detonation and PT burnout may happen. Based on the analysis of ferroresonance over voltage mechanism, various kinds of countermeasure to prevent ferroresonance over voltage in PT are analyzed:PT delta connection winding connected with resistance or frequency division resonance apparatus;neutral point earthed via resistance or XXQ?10;PT neutral point connected with single phase PT,anti resonance PT.Some experiences in the selection of PT type and their applicable coverage are presented the reformation.It would be useful in the reformation of urban network and the set up of new substation.
作者 张玲 郝春娟
出处 《电力自动化设备》 EI CSCD 2000年第3期29-31,共3页 Electric Power Automation Equipment
关键词 铁磁谐振 消谐器 过电压 电压互感器 城市电网 ferroresonance vibration absorber anti-resonance PT excess voltage
  • 相关文献

参考文献4

  • 1陈维贤.内过电压基础[M].北京:电力工业出版社,1981
  • 2李达坚,何毅思,冯庆燎.10 kV电压互感器各种防谐振措施评述[J].广东电力,1999,12(1):34-37. 被引量:6
  • 3张旭俊.JSJW型电压互感器的设计改革和三相铁谐振现象的机理[J].电力技术,1980,(2):40-45.
  • 4罗国祥.电压互感器分频谐振及消振措施的试验与分析[J].山西电力技术,1981,(2):40-41.

共引文献7

同被引文献262

引证文献33

二级引证文献245