期刊文献+

应用机电暂态程序判断直流换相失败的分析 被引量:2

Analysis of DC Commutation Failure Judgment Through Electromechanical Transient Program
在线阅读 下载PDF
导出
摘要 换相失败是直流系统常见的故障之一,连续换相失败或者多回直流同时换相失败,将会严重危害交直流系统的稳定运行。因此,换相失败的判断是一个非常重要的问题。机电暂态程序具有模型简单、仿真规模大、计算时间短等特点,而且仿真精度能够满足电力系统的计算要求,常常用于分析大型交直流混合电网的换相失败原因。在阐述换向失败的机理及其影响因素的基础上,分析了机电暂态程序的直流模型和换相失败判据,并且通过一算例计算,比较了国内常用的机电暂态程序BPA和PSS/E的仿真结果,着重分析了两个程序用于换相失败研究的范围。 Commutation failure is one of the common faults of DC system,continuous commutation failure or multiple HVDC commutation failure will seriously endanger the stable operation of the AC and DC systems,and thus commutation failure judgment is a very important issue.Electromechanical transient program often has simple models,large simulation scale,short computation time,and it's simulation accuracy can meet the power system calculation requirements,so it is often used for large AC-DC hybrid grid commutation failure research.This paper describes the commutation failure mechanism and its influencing factors first,then analyzes the DC models and commutation failure criterion of electromechanical transient program.Finally,compare the simulation results of the most commonly used electrome-chanical transient program BPA and PSS/E through an example,and analyze the scope of these two programs for commutation failure research.
出处 《电力与能源》 2013年第1期42-46,共5页 Power & Energy
关键词 换相失败 交直流 机电暂态 Commutation failure AC and DC systems Electromechanical transient program
  • 相关文献

参考文献12

二级参考文献104

共引文献433

同被引文献49

引证文献2

二级引证文献10

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部