湖南地区土壤源热泵制冷运行特性的实验研究

Experimental Study on Cooling Operation Characteristics of Soil Source Heat Pump in Hunan
在线阅读 下载PDF
导出
摘要 以南华大学土壤源热泵系统为研究对象,对夏季制冷运行特性进行实验研究。测得了热泵运行前土壤原始温度分布,测试了热泵机组连续和间隙运行时,管壁处土壤温度变化情况,埋管侧进出口水温的变化情况以及埋管换热器的换热情况。研究结果表明:土壤原始温度为19.77℃,与连续运行相比,间隙运行下管壁处土壤温度降低了2.3℃,埋管侧进出口水温分别降低了2℃和2.3℃,单位管长深换热量提高了25%。 With the soil source heat pump system of Nanhua University as an example, investigated the operating characteristics of cooling conditions in summer. Measured the initial soil temperature distribution before heat pump operating, and tested respectively the soil temperature changed, the inlet and Outlet water temperature in the underground exchanger and the heat transfer capacity under continuous and intermittent cooling operation. The results indicated that under the intermittent operation at the soil initial temperature of 19.77 ℃, the soil temperature was increased by 2.3 ℃, inlet and outlet water temperature were increased by 2 ℃ and 2.3 ℃ , and the unit well depth change heat increased by 25%, respectively, when compared with continuous operation.
出处 《湖南工业大学学报》 2012年第5期30-32,45,共4页 Journal of Hunan University of Technology
关键词 土壤源热泵 制冷工况 换热特性 实验研究 soil source heat pump refrigeration conditions heat transfer characteristics experimental study
  • 相关文献

参考文献9

  • 1Hepbasli A, Akdemir O, Hancioglu E. Experimental Study of a Closed Loop Vertical Ground Source Heat Pump System [J]. Energy Conversion and Management, 2003, 44(4): 527-548.
  • 2Hang Yujin, Lee Jaekeun, Jeong Youngman, et al. Cooling Performance of a Vertical Ground-Coupled Heat Pump System Installed in a School Building[J]. Renewable Energy, 2009(34): 578-582.
  • 3Lund J W, Freeston D K, Boyd T L. Direct Application of Geothermal Energy 2005 Worldwide Review[J]. Geothermics, 2005, 34(6): 691-727.
  • 4Blum Philipp, Campillo Gisela, Munch Wolfram, et al. CO2 Savings of Ground Source Heat Pump Systems-A Regional Analysis[J]. Renewable Energy, 2010, 35(1): 122-127.
  • 5Ozyurt Omer, Ekinci Dundar Arif. Experimental Study of Vertical Ground-Source Heat Pump Performance Evaluationfor Cold Climate in Turkey[J]. Applied Energy, 2011, 88 (4): 1257-1265.
  • 6Hepbasli Arif, Akdemir Ozay, Hancioglu Ebru. Experimental Study of a Closed Loop Vertical Ground Source Heat Pump System[J]. Energy Conversion and Management, 2003, 44(4): 527-548.
  • 7Bi Yuehong, Guo Tingwei, Zhang Liang, et al. Solar Ground Source Heat Pump System[J]. Applied Energy, 2004, 78(2): 231-245.
  • 8Bi Yuehong, Chen Lingen, Wu Chih. Ground Heat Exchanger Temperature Distribution Analysis and Experimental Verification[J]. Applied Thermal Engineering, 2002, 22(2): 183-189.
  • 9郑红旗,张建忠,陈九法.地埋管换热器形式、管径及岩土温度对其换热性能的影响[J].暖通空调,2012,42(5):90-95. 被引量:12