期刊文献+

高压交流输电线路电晕可听噪声机理及理论模型 被引量:13

Mechanism and Theoretical Model for Corona Audible Noise from High Voltage AC Transmission Lines
在线阅读 下载PDF
导出
摘要 为预估高压交流输电导线产生的电晕可听噪声,研究了电晕可听噪声的产生机理及其理论预估模型.高压交流输电线电晕产生正负离子,基于Drude模型研究了正负离子的运动规律,进而阐明了电晕可听噪声的产生机理.在此基础上,进一步运用Kirchhoff公式得出电晕可听噪声的理论预估模型,并针对特定导线布置形式计算了典型的二倍工频分量的声压及声场分布.数值计算结果表明,可听噪声中的二倍工频分量衰减缓慢,且在导线附近区域存在显著的干涉现象,计算的结果会随着离子浓度的变化而变化,但声压级分布曲线的形状不会变化.该模型适合于电晕可听噪声的计算,有助于指导输电线设计. To predict the levels of corona audible noise resulting from high voltage AC power transmission lines, the mechanism of corona audible noise and its theoretical prediction model are investigated. On the basis of the Drude model, the motion of positive and negative ions produced by corona of high voltage AC power transmission lines is analyzed and the mechanism of corona audible noise is explained. In terms of Kirchhoff formula, the theoretical prediction model is established, and for a certain line configuration, the acoustic field distribution of the typical component with twice power frequency is computed. The numerical result shows that the audible noise component with twice power frequency attenuates slowly and leads to an obvious interference near the transmission lines. The magnitude of sound pressure level distribution curve undulates with the ion concentration, but the shape gets unchanged. The model is suitable for evaluating levels of corona audible noise to guide transmission line designs.
出处 《西安交通大学学报》 EI CAS CSCD 北大核心 2012年第8期128-132,共5页 Journal of Xi'an Jiaotong University
基金 教育部新世纪优秀人才支持计划资助项目(NCET-09-0644) 中央高校基本科研业务费专项资金资助项目
关键词 电晕可听噪声 Drude模型 二倍工频分量 corona audible noise Drude model twice power frequency component
  • 相关文献

参考文献14

  • 1谭闻,张小武.输电线路可听噪声研究综述[J].高压电器,2009,45(3):109-112. 被引量:38
  • 2COMBES M G, CARBERRY R E, CHARTIER V L, et al. A comparison of methods for calculating audible noise of high voltage transmission lines [J]. IEEE Transactions on Power Apparatus and Systems, 1982, 101(10) :4090-4099.
  • 3唐剑,杨迎建,李永双,张广洲,张小武,何金良.特高压交流输电线路电晕效应的预测方法,Ⅰ:可听噪声[J].高电压技术,2010,36(11):2679-2686. 被引量:35
  • 4PERRY D E. An analysis of transmission line audible noise levels based upon field and three-phase test line measurements [J]. IEEE Transactions on Power Ap-paratus and Systems, 1972, 91(3):857-865.
  • 5TANABE K. Second harmonics of audible noise from AC transmission lines: random walk model on space distribution[J]. IEEE Transactions on Power Delivery, 1991, 6(1) :216-222.
  • 6STRAUMANN U, FAN Jianbin. Audible noise from AC-UHV transmission lines: theoretical comparison of broadband and tonal components[EB/OL]. [2012-01- 10]. http://www, eeh. ee. ethz. ch/en/no_cache/pow- er/high-voltage-laboratory/publications/conference-pa- pers. html.
  • 7STRAUMANN U. Mechanism of the tonal emission From ac high voltage overhead transmission lines[J].Iournal of Physics: D Applied Physics, 2011, 44 (7) : 075501.
  • 8邱海宾,杨坤德.基于波叠加的高压输电线噪声场计算模型[J].电声技术,2009,33(10):81-85. 被引量:4
  • 9MAZZOLA M S, MOLEN G M. Modeling of a dc glow plasma loudspeaker [J]. Journal of the Acous tical Society of America, 1987,81 (6) : 1972-1978.
  • 10ASHCROFT N W, MERMIN N D. Solid state phys ics [M]. Beijing: World Publishing Corp., 2004:1-11.

二级参考文献41

  • 1吴桂芳.我国±500kV直流输电工程的电磁环境问题[J].电网技术,2005,29(11):5-8. 被引量:61
  • 2邬雄,万保权,路遥.1000kV级交流输电线路电磁环境的研究[J].高电压技术,2006,32(12):55-58. 被引量:71
  • 3唐剑,何金良,杨迎建,陈维江,邬雄,谷山强.特高压电晕笼防护段的设计[J].高电压技术,2007,33(3):17-20. 被引量:23
  • 4唐剑,杨迎建,何金良,陈维江,邬雄,谷山强.1000kV级特高压交流电晕笼设计关键问题探讨[J].高电压技术,2007,33(4):1-5. 被引量:38
  • 5Electric Power Research Institute.Transmission Line Reference Book 345 kV and Above, 2nd Edition[M]. Palo Alto, California: Electric Power Research Institute, 1987.
  • 6TAYLOR E R, CHARTIER V L, RICE D N. Audible Noiseand Visual Corona from HV and EHV Transmission Lines and Substation Conductors Laboratory Tests[J]. IEEE Transactions on Power Apparatus and Systems, 1969, 88 (5):666- 679.
  • 7COMBER M G, NIGBOR R J. Audible Noise Performance of Regular and Asymmetric Bundles and Effect of Conductor Aging on Project UHV's Three-phase Test Line [J]. IEEE Transactions on Power Apparatus and Systems, 1979, 98(2): 561-572.
  • 8VINH T, SHIH C H, KING J V,et al. Audible Noise and Corona Loss Performance of 9-conductor Bundle for UHV Transmission Lines[J]. IEEE Transactions on Power Apparatus and Systems, 1985, 104(10): 2764-2770.
  • 9LUNDQUIST J. Results from A.C Transmission Line Audible Noise Studies at the Anneberg EHV Test Station [J]. IEEE Transactions on Power Delivery, 1990, 5(1): 317-323.
  • 10LEKGANYANE M J, IJUMBA N M, BRITTEN A C. Corona Audible Noise Measurements in a Small Indoor Corona Cage under HVDC Voltages [C]// 2006 International Conference on Power System Technology, New York, USA, 2006: 1-5.