摘要 串联电容及其非线性保护装置给串联补偿线路的故障测距带来了困难。在考虑串联电容及其保护装置对频率提取及边界条件影响的基础上,研究了基于行波固有频率的串补输电线路故障测距算法。该算法首先利用单端电流频率信息判断故障发生在串联电容前或串联电容后,对于发生在串联电容后的故障,需要考虑串联电容处的折反射对测距算法的影响,然后依据故障距离与固有频率、边界条件间的数学关系进行精确测距。大量仿真结果表明该算法不受故障距离、故障类型和过渡电阻的影响,具有良好的测距精度和适应性。 Series capacitor and its nonlinear protection bring troubles to fault location of transmission line with series compensator. Considering the influence of series capacitor and its protection device on frequency extraction and boundary conditions, based on natural frequencies of travelling wave a fault location algorithm for transmission line with series compensator was researched. Firstly, by use of frequency information of single terminal current it was judged that the fault occurred in the front of or behind the series capacitor; for the fault occurred behind the series capacitor it was necessary to consider the influences of refraction and reflection of travelling wave at series capacitor on fault location algorithm, then precise fault location was performed according to mathematical relation among fault distance, natural frequencies of travelling wave and boundary conditions. A lot of simulation results showed that the proposed algorithm was independent of fault distance, fault types and transition resistance, and possessed satisfied fault location accuracy and adaptability.
出处 《电网技术》 EI CSCD 北大核心 2012年第6期71-76,共6页 Power System Technology
基金 国家自然科学基金资助项目(50877068) 高等学校博士学科点专项科研基金资助项目(200806130004) 中央高校基本科研业务费专项资金资助(SWJTU11ZT07)~~
关键词 串补线路 氧化锌非线性电阻 固有频率 故障测距 series compensated line metal oxide varistor natural frequency fault location
  • 相关文献

参考文献15

二级参考文献91

  • 1覃剑.输电线路单端行波故障测距的研究[J].电网技术,2005,29(15):65-70. 被引量:89
  • 2王绍部,舒乃秋,龚庆武,陈玉林,杨振东.计及TA传变特性的输电线路行波故障定位研究[J].中国电机工程学报,2006,26(2):88-92. 被引量:16
  • 3鲁文,徐晨亮,丁孝华,孙国城,徐石明.一种考虑分布电容的模糊故障测距算法[J].电力系统自动化,2006,30(8):57-60. 被引量:15
  • 4郭俊宏,杨以涵,谭伟璞,孙建锋,游耀丽.中压配电网的故障测距实用化方法[J].电网技术,2006,30(8):76-80. 被引量:31
  • 5陈玥云,覃剑,王欣,陈树勇,张冰冰,于玉泽.配电网故障测距综述[J].电网技术,2006,30(18):89-93. 被引量:58
  • 6贺家礼 宋从矩(He Jiali Song Congju).电力系统继电保护原理(Principle of relay protection)[M].北京:中国电力出版社(Beijing:Hydro-electrical Press),1994.10.
  • 7施围(Shi Wei).电力系统过电压计算(Calculation of power system over voltage)[M].西安: 西安交通大学出版社(Xi''An: Xi''an Jiaotong University Press),1988.12.
  • 8Murari M, Bogdan K, Eugniusz R, et al. First zone algorithm for protection of series compensated lines[J]. IEEE Transactions on Power Delivery, 2001, 16(2): 200-207.
  • 9浙江省电力中心实验所高压实验组,浙江大学发电教研室.串联电容补偿装置在电力系统中的应用[M].北京:水利电力出版社,1976:41-125.
  • 10Komm R W, Hill F, Howe R. Empirical mode decomposition and Hilbert analysis applied to rotation residuals of the solar convection zone[J]. Astrophysical Journal, 2001, 558(1): 428-441.

共引文献289

同被引文献215

引证文献14

二级引证文献132

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部