摘要
本文结合某教学楼中央空调节能改造工程,基于空调负荷特性,分析不同冷冻水泵变频控制方式的节能性,分析不同控制方式对水泵及机组能耗的影响,计算综合节能率,并结合工程实际得出最优控制方式为干管定温差控制(综合节能率为60.5%)。
The water stability,energy-saving performance and the effects of energy consumption of pumps and chillers under conditions of different frequency conversion control strategies are analysed,which is based on the air conditioning load in the central air conditioning energy-saving renovation project of a special teaching building.Comprehensive energy saving rate is calculated and the control strategy of main pipe constant differential temperature whose comprehensive energy saving rate is 60.5% is determined as the optimum control strategy.
出处
《建筑热能通风空调》
2012年第2期49-52,共4页
Building Energy & Environment
关键词
冷冻水
变流量
压差控制
定温差控制
综合节能率
chilled water
variable flow
differential pressure control
constant differential temperature control
comprehensive energy saving rate