期刊文献+

基于Matlab电弧模型低压断路器仿真 被引量:5

Simulation of Arc Model of Low Voltage Circuit Breaker Based on MATLAB
在线阅读 下载PDF
导出
摘要 通过对低压断路器实验数据进行分析,在matlab中利用最小二乘法计算出Mayr电弧模型的相关参数,并利用Simulink建立简化的低压断路器开断短路电流的模型。仿真所得的结果与实验数据相比较接近,表明该方法对低压断路器开断动作的定性分析有一定参考价值。 By the analysis of the experimental data of a low voltage circuit breaker, use leastsquare method to calculate the relevant parameters of Mayr are model in Matlab. And use Simulink to establish a simplified breaking short-circuit current model of the low voltage circuit breaker. The simulation results are close with the experimental data. It shows that the method has a certain referenee value to the qualitative analysis of the breaker breakig action.
作者 张忠坚
出处 《电气开关》 2012年第2期41-42,46,共3页 Electric Switchgear
关键词 低压断路器 电弧模型 最小二乘法 仿真 low-voltage breaker arc model least square method simulation
  • 相关文献

参考文献8

  • 1黄永红;张新华.低压电器[M]北京:化学工业出版社,2007.
  • 2王其平.电器中的电孤理论[M]上海:上海科学技术出版社,19639.
  • 3吴天明;谢小竹;彭彬.MATLAB电力系统设计与分析[M]北京:国防工业出版社,2004.
  • 4W.Gimenez,O.Hevia. " Method to Determine theParameters of the Electric Arc from Test Data,"[A].Universidad Tecnologica Nacional,Fac.Reg.Santa Fe,Argentina,2000.41-45.
  • 5Schavemaker P H,Van der Sluis L. An improvedmayr-type arc model based on current-zero mea-surements[J].IEEE Transactions on Power Delivery,2000,(02):580-584.
  • 6张德丰.MATLAB-Simulink建模与仿真[M]北京:电子工业出版社,2009.
  • 7黄绍平,杨青,李靖.基于MATLAB的电弧模型仿真[J].电力系统及其自动化学报,2005,17(5):64-66. 被引量:89
  • 8陈德桂.低压电弧故障断路器——一种新型低压保护电器[J].低压电器,2007(3):7-9. 被引量:39

二级参考文献8

  • 1Schavemaker P H.Arc model blockset[DB].Power Systems Laboratory,Delft University of Technolog-y,the Netherlands(eps.et.tudelft.nl),2001.
  • 2Habedank U.On the mathematical description of arc behaviour in the vicinity of current zero[J].etzArchiv,Vot,No.11,1988,10(11):339-343.
  • 3Van der Sluis L,Rutgers W R,Koreman C G A.A physical arc model for the simulation of current zero behwior of high-voltage circuit breakers[J].IEEE Trans on Power Delivery,1992,7(2):1016-1022.
  • 4Schavemaker P H,Van der Sluis L.An improved mayr-type arc model based on current-zero measurements[J].IEEE Trans on Power Delivery,2000,15(2):580-584.
  • 5Smeets R P P,Kertesz V.Evaluation of high-voltage circuit breaker performance with a validated arc model[J].IEE Proceedings-Generation,Transmissio-n and Distribution,2000,147(2):121-125.
  • 6BRANSTON D W. Innovation in Low Voltage Switching Technology [ C ]//21st International Conference on Electrical Contacts. Swityerland, 2002:283-289.
  • 7MECHLER P. Simnlation of AC Arc Faults in Aircraft Electrical Networks [C]//21st International Conference on Electrical Contacts. Swityerland, 2002 : 290- 295.
  • 8HETYMANNSEDER E, ZUERCHER J C, HASTINGS J K. Method for Realistic Evaluation of Arc Faults Detection Performance [C]//21st International Conference on Electrical Contacts. Swityerland, 2002 : 296- 302.