期刊文献+

蒸发冷却空气处理机组的性能测试与分析 被引量:4

Performance Test and Analysis of Evaporative Air Handing Units
在线阅读 下载PDF
导出
摘要 以一台蒸发冷却空气处理机组为测试对象,该机组设有惯性粗效过滤器、袋式中效过滤器、亲水性高分子纤维填料、双风机。对其进行样机测试,得到了其送风量、风速、温度、相对湿度、阻力等性能参数。通过计算分析得到了不同室外温度下,填料直接蒸发冷却对空气相对湿度的影响与室外空气的相对湿度有关,室外相对湿度越高,相对湿度提高的程度就越高,同时填料的效率也是随着室外干湿球温度的变化而变化。由于本次测试机组采用双风机系统,通过测试发现了双风机系统的总送风量并不是两台风机风量的简单叠加,为以后的工程设计提供了参考依据。 According to the test of evaporative air handing units, it was consisted of an inertial coarse filter, bag type filter, the hydrophilic polymer fiber filler, double fan. The test can obtain the air flow, wind speed, temperature, relative humidity, resistance and other performance parameters. Through the analysis , the increase of the relative humidity of outdoor air depend on he relative humidity of outdoor air. At the same time that the efficiency of the filling changed with the outdoor dry and wet bulb temperature. The air conditioning handing units used double fan,it found the the total volume is not the superimposed volume of the two fans. it was provide a reference for future design.
出处 《流体机械》 CSCD 北大核心 2012年第3期67-70,共4页 Fluid Machinery
关键词 蒸发冷却 空调机组 常规岛 填料 测试分析 evaporative air handing units conventional island filler test and analysis