摘要
文章研究了发电机中性点经消弧线圈接地系统考虑燃熄弧条件、发电机不对称度、调谐度、品质因数Q 值的影响等因素时的单相间歇电弧接地过电压,研究结果表明,前两者对暂态过电压的影响较大。对发电机组甩负荷和频率变化时发生单相间歇电弧接地的暂态过电压进行了计算,计算表明动态电势是主要的影响因素。
The single phase intermittent arc grounding overvoltage of generator neutral with resonant grounding is studied while the influences of several factors are considered, such as the condition of arc burning and clear, unsymmetry extent of generator, tuning degree and the quality factor Q. The calculating result indicates the first two factors have larger effects on this transient overvoltage. The transient overvoltage, caused by single phase intermittence arc grounding while the load of generator is shed or the frequency varies, is calculated. Analysis results indicate that the dynamic potential is the major factor effecting the transient overvoltage, and some corresponding countermeasures are suggested.
出处
《电网技术》
EI
CSCD
北大核心
2000年第2期14-16,19,共4页
Power System Technology