异频法测量长线路工频参数的误差分析及校正 被引量:10

Error analysis and correction of long line power frequency parameters measured by varying frequency method
原文传递
导出
摘要 基于长线分布参数模型对输电线路开路阻抗和短路阻抗进行了仿真分析和模型试验,分析了异频法单端测量超长距离交直流输电线路工频参数时由分布参数影响造成的测量误差,直流输电线路的工频参数的现场测试数据验证了分析结果,并依据分布参数模型进行数据校正,解决了长线路尤其是直流输电线路工频参数的测量误差问题. Basing on the transmission lines distributed parameter model,the open-circuit and short-circuit impedances of power line are simulated and tested.The error caused by the distribution parameters impact is analyzed when the frequency parameters of ultra-long AC DC power line are measured through varying frequency method with single-ended.The field test data of the DC power line frequency parameters verified the simulation results;and the data correction is performed based on the distributed parameter model to eliminate frequency parameters measurement error of the long power line,especially the DC power line.
出处 《武汉大学学报(工学版)》 CAS CSCD 北大核心 2012年第1期111-115,共5页 Engineering Journal of Wuhan University
关键词 长线路 异频法 分布参数模型 工频参数 误差分析 数据校正 long power line varying frequency method distributed parameter model power frequency parameters error analysis data correction
  • 相关文献

参考文献6

  • 1GB50233-2005 110-500 kV架空送电线路施工及验收规范[S].
  • 2黄明祥,黄一丹.干扰电压下线路阻抗测量方法的探讨[J].电力建设,1994,15(5):59-64. 被引量:10
  • 3许荣生.电源倒极性法测试线路零序阻抗[J].华东电力,1991,19(7):10-14. 被引量:4
  • 4Di Shi, Daniel J Tylavsky, Kristian M Koellner, Naim Logic, David E Wheeler. Transmission line parameter identification using PMU measurements [J]. European Transactions on Electrical Power, 2011,21 (4): 1574- 1588.
  • 5孔金欧,吴季.电磁波理论[M].北京:电子工业出版社,2005.
  • 6蔡成良.荆门-上海±500kV直流输电线路参数测试报告[R],2011.