期刊文献+

采用三闭环控制的超低频高压电源设计 被引量:2

Design of Very Low Frequency High Voltage Generator Using Three-closed-loop Control
原文传递
导出
摘要 为了满足交联聚乙烯(XLPE)电缆对检测电源的要求,设计了一种采用两个高频高压变压器作为升压变压器的超低频高压电源。详细阐述了系统的硬件设计及软件控制策略,优化了变压器的结构及绝缘,大大缩小了变压器的体积及质量,减小了变压器的分布参数。并根据电路拓扑的特点,首次采用先进的三闭环控制技术,动态地对高频部分及低频部分的输出进行了监控与调整,减小了高频高压变压器分布参数对电源性能的影响。同时对采样数据采取了分段化的处理方法,大大减小了程序的计算量,使它能够应用于单片机控制。采用所设计的35kV/0.1Hz电源对电气特性等效于XLPE电缆的高压电容(1.5μF)进行了实验,其总谐波畸变率(THD)为2.76%,完全满足IEEE 400.2标准对总谐波畸变率<5%的要求。实验结果验证了理论的可行性与正确性。 A novel topology and the control strategy of the very-low-frequency(VLF) high voltage generator are introduced to meet the requirements of XLPE cable test.Design parameters of the system hardware and the control strategy of the system software are presented.The structure and the insulation of the transformer are optimized.As a result,the volume and the weight are decreased obviously.According to the topology of the circuit,the cutting edge of three-closed-loop control technology is first applied in VLF high voltage power supply.The output voltage and the secondary voltage are timely monitored and regulated,so that the influence of distributed parameter is reduced effectively.Simultaneously,the principle of segmental data processing is applied in data processing.Thereby,the calculation complexity is decreased significantly.The 35 kV/0.1 Hz power supply is used to test a 1.5 μF capacitor.Total harmonic distortion is 2.76% which can meet the requirements of IEEE 400.6 standard.The experimental results verify the accuracy and feasibility of the theory.
出处 《高电压技术》 EI CAS CSCD 北大核心 2012年第2期490-496,共7页 High Voltage Engineering
基金 国家高技术研究发展计划(863计划)(2008AA03A325)~~
关键词 超低频(VLF)高压 电源 三闭环控制 串并联谐振(LCC)变换器 分段化数据处理 XLPE电缆检测 very low frequency(VLF) high voltage generator three-close-loop control LCC resonant converter segmental data processing XLPE cable test
  • 相关文献

参考文献28

  • 1Katsumi Uchida, Yoichi Kato, Masahiko Nakade, et al. Esti- mating the remaining life of water treed XLPE cable by VLF voltage withstand tests [J]. Furukawa Review, 2001(20): 65- 70.
  • 2Eager G S, Katz C, Fryszczyn B, et al. High voltage VLF tes- ting of power cables [J]. IEEE Transactions on Power Deliver- y, 1997, 12(2): 565-570.
  • 3Eager G S, Fryszczyn B, Katz C, et al. Effect of DC testing wa- ter tree deteriorated cable and a preliminary evaluation of VLF as alternate[J]. IEEE Transactions on Power Delevery, 1992, 7(3) : 1582-1589.
  • 4Alain Jaafari, Geza Joos. A compact high voltage low frequency power supply [C]// Conference Proceedings of 1995 Applied Power Electronics Conference and Expositon (APEC 1995). Dallas, TX, USA: IEEE, 1995:821-825.
  • 5Hendriks J, Brussaard G J H. Picosecond high voltage switching of pressurized spark gap [C]// Digest of Technichal of 2003 Pulsed Power Conference(PPC 2003): No 1. [S. l. ]: IEEE, 2003: 587-590.
  • 6Seesanga S, Kongnun W, Sangswang A, et al. A new type of the VLF high voltage generator[C]// Proceedings of Conference on Electrical Engineering--Electronics, Computer, Telecommu- nications and Information Technology(ECTI-CON 2008) : No 2. Seoul, South Korea: IEEE, 2008: 929-932.
  • 7Kongnun W, Sangswang A, Chotigo S. A cascaded H-bridge converter for a new type of the VLF high voltage generator[C] // Proceedings of the 9th International Conference on Properties and Applications of Dielectric Materials. Harbin, China: [s. n. ], 2009.. 89 92.
  • 8Seesanga S, Kongnun W, Chotigo S. Microcontroller modula- tion for VLF high voltage generator rate 3' kV peak using DSPIC30F2010[C]// 2nd IEEE International Conference on Power and Energy(PECon 2008). Johor Baharu, Malaysia: IEEE, 2008:62-66.
  • 9赵艳雷,童建忠,齐智平.25kV高精度直流负高压源设计[J].高电压技术,2006,32(4):88-90. 被引量:15
  • 10高迎慧,孙鹞鸿,严萍,石一.40kW高功率密度数字化控制充电电源[J].强激光与粒子束,2009,21(8):1259-1262. 被引量:19

二级参考文献86

共引文献115

同被引文献11

引证文献2

二级引证文献12

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部