针对韶钢某变电站110 kV的GIS设备一SF6气室压力异常升高的情况,判断是气室内漏造成的结果,并采取了检查、更换气室盆式绝缘子的处理措施,恢复了气室的正常压力,确保了该站GIS设备的正常运行。提出了3点建议,避免类似故障的发生。
A fault of abnormal pressure raising in the SF6 gas chamber of 110 kV GIS in a substation at Shaoguan Iron & Steel Group Co., Ltd. was analyzed, and the cause was judged to be the air-leakage. Then the chamber was checked, and the pot-type insulator was replaced. recovered. Puts forward three suggestions are offered in this Consequently, the pressure of the gas chamber was paper to avoid this kind of fault.