摘要
对结构高度为492m的上海环球金融中心大楼顶部实测到的良态强风时段下的平均风速和脉动风速数据进行了分析,得到了3s、10min以及1h时距下的平均风速值,并对其进行线性拟合.结果表明,10min平均风速与3s平均最大(瞬时最大)风速的比值约为0.876 8.根据实测数据,还分析了湍流度和阵风因子,结果表明,湍流度和阵风因子均随平均风速的增大而减小,此外,对比了部分时段内的实测脉动风速功率谱密度与Von-Karman谱,两者较为吻合.
The mean and fluctuating wind speed data of strong wind of normal climate measured on the top of Shanghai World Financial Center with a height of 492 m were analyzed.Mean wind speeds in different intervals of 3 s,10 min and 1 hour were separately computed.The results showed that the averaged mean wind speed ratio between 10 min mean wind speed and 3 s maximum mean wind speed was approximately 0.876 8.The formulas for the ratios were then derived by using curve-fitting technique.The turbulence intensity,gust factor were also computed based on the measured data.The results indicate that both turbulence intensity and gust factor decrease with the increase of mean wind speed.In addition,the power spectral densities of fluctuating wind speeds are in agreement with the Von-Karman spectrum.
出处
《同济大学学报(自然科学版)》
EI
CAS
CSCD
北大核心
2011年第11期1592-1597,共6页
Journal of Tongji University:Natural Science
基金
国家自然科学基金重大研究计划重点项目(90715040)
关键词
实测
平均风速
脉动风速
湍流度
阵风因子
功率谱密度
field measurement
mean wind speed
fluctuating wind speed
turbulence intensity
gust factor
power spectral density