IDC机房用板式换热器的节能实例分析 被引量:4

Analysis of actual energy-saving case on application of plate heat exchanger into IDC computer room
在线阅读 下载PDF
导出
摘要 在分析当前IDC机房高能耗背景的基础上,结合某IDC机房的空调节能改造实例,对改造后的节电效果进行理论计算与实际测试。结果表明,通信机房用板式换热器的节电效果是显著的,节电率达14.6%,回收期为2.25年,具有良好的经济效益和社会效益。 Based on the analysis of higher energy consumption in current IDC computer room,combined with one engineering case of the energy-saving renovation of air-conditioning in one IDC computer room,calculates theoretically and tests actual the energy-saving effect of the renovated computer room.The result shows that,the energy-saving effect of the method that the plate heat exchanger is used in IDC computer room is remarkable,and the power saving rate is up to 14.6%,recovery period is 2.25 year,and the energy-saving renovation of the IDC computer room has good economic benefit and social benefit.
出处 《制冷与空调》 2011年第2期97-99,110,共4页 Refrigeration and Air-Conditioning
关键词 IDC机房 空调 板式换热器 节能改造 回收期 IDC computer room air-conditioning plate heat exchanger energy-saving renovation recovery period