摘要 根据紫外测量法[5]获得的绝缘子放电强度,提出了采用模糊推理对绝缘子外绝缘放电状况进行评估的方法。该方法首先测量绝缘子电晕放电产生的紫外光脉冲数量,同时采集环境温度、湿度信息,根据在线监测的数据分析确定各输入量之间的关系,建立了一系列可用于模糊推理的模糊子集,并对其隶属度函数进行了推导,建立详尽的模糊推理规则,进行模糊推理,判断其外绝缘放电状况。最后,针对现场挂网试验数据,采用Simulink进行仿真分析,验证了该方法的有效性。 In this paper,a method based on the fuzzy theory and ultra-violet(UV) radiation measurement to ac-cess the discharge status of external insulation of the insulator is presented.In this method,the amount of UV pul-ses generated by corona discharge of insulator is measured firstly,while collecting temperature of environment and humidity information,and then the relationship between the inputs is confirmed by analyzing online monitoring da-ta,a series of fuzzy sets for fuzzy reasoning is set up,and the membership function is derived,fuzzy inference rules are established.Then the fuzzy reasoning is carried out to estimate the discharge status of external insulation.Final-ly,the validity of this method is verified by simulating and analyzing the data detected from the tests of connecting to grid in Simulink.
出处 《电工电能新技术》 CSCD 北大核心 2011年第2期79-83,共5页 Advanced Technology of Electrical Engineering and Energy
基金 第四届国家大学生创新性实验计划资助项目(101061115)
关键词 电晕放电 紫外脉冲 外绝缘放电状况 模糊推理 SIMULINK corona discharges ultra-violet pulse discharge status of external insulation fuzzy reasoning Simu-
  • 相关文献

参考文献7

二级参考文献20

  • 1王国利,郝艳捧,李彦明.变压器局部放电特高频在线监测系统的研究[J].电工电能新技术,2004,23(4):18-23. 被引量:13
  • 2梁曦东,戴建军,周远翔,陈以方.超声法检测绝缘子用玻璃钢芯棒脆断裂纹的研究[J].中国电机工程学报,2005,25(3):110-114. 被引量:46
  • 3Kawada H, Honda M, Inoue T, et al. Partial discharge automatic monitor for oil-filled power transformer[J]. IEEE Trans. on Power Apparatus and Systems, 1984, 103(2) : 422- 428.
  • 4Raja Kuppuswamy. On the UHF partial discharge measurement in transformers [A]. 2003 Annual Report Conference on Electrical Insulation and Dielectric Phenomena [ C]. 2003. 349-352.
  • 5Judd M D, Cleary G P, Bennoch C J. Applying UHF partial discharge detection to power transformers [ J ]. IEEE Power Eng. Review, 2002, 22 (8): 57-59.
  • 6GB/T7354-2003/IEC60270:2000,局部放电测量.
  • 7[1]The MathWorks Inc.. Fuzzy logic toolbox user's guide.2002, 13~26.
  • 8Rutgers W R,10th ISH,1997年,25页
  • 9邱昌容,电工设备局部放电及其测试技术,1994年
  • 10VAILLANCOURT G H,BELLERIVE J P,ST-JEAN M,et al.New live line tester for porcelain suspension insulators on high-voltage power lines[J].IEEE Trans on Power Delivery,1994,9(1):208-219.