隔离开关不同操作方式产生的快速暂态过电压 被引量:25

Very Fast Transient Overvoltage Caused by Different Switching Modes of Disconnector
在线阅读 下载PDF
导出
摘要 超高压GIS内开关操作引起的快速暂态过电压严重威胁了电力系统运行的安全性。笔者针对某550 kVGIS,建立了仿真模型并确定了相关参数,研究了多种运行方式、隔离开关不同操作条件下GIS内部各节点的快速暂态过电压,得到了操作顺序对过电压的影响规律,同时分析了隔离开关并联电阻对快速暂态过电压的抑制作用。结果表明,隔离开关分闸操作产生的过电压幅值远大于其合闸操作产生的过电压;切换母线操作产生的过电压较严重;被操作开关处的VFTO受操作方式影响最大;隔离开关并联电阻加速了过电压的衰减抑制效果明显,但GIS整体成本增加,电阻值大于200Ω时VFTO幅值小于1.6 p.u.。 Operating experiences have shown that the very fast transient overvoltage(VFTO) caused by switching operations in extra high voltage gas insulated substation(GIS) threatens the security of power system.For a 550 kV GIS,the model has been built up and the parameters have been selected in this paper.Taking different operating modes into consideration,the magnitudes and frequency spectrum of VFTO along GIS nodes have been calculated by using EMTP.The relationships between switching modes and VFTO have been founded.The protective effect on VFTO of parallel resistor has also been studied.It is shown that the VFTO caused by opening operations are even higher than those caused by closing operations.Switching conditions and operating modes would exert an influence on VFTO,even for the node of the switches operated.The VFTO caused by switching one bus to the other is the most severe.Parallel resistors could accelerate the attenuation of overvoltages,the magnitudes of which will be less than 1.6p.u.,when the resistance is more than 200 Ω.
作者 刘青
出处 《高压电器》 CAS CSCD 北大核心 2011年第4期17-22,共6页 High Voltage Apparatus
基金 陕西省教育厅科研计划资助项目(项目批准号09JK578)~~
关键词 气体绝缘变电站 快速暂态过电压 操作方式 并联电阻 GIS VFTO switching modes parallel resistor
  • 相关文献

参考文献9

二级参考文献27

  • 1刘青,赵峰,陈梁金,施围,于睁.330kV GIS中投切电抗器的过电压研究[J].高压电器,2004,40(5):358-360. 被引量:9
  • 2何善庆.GIS中的快速暂态现象[J].高压电器,1995,31(2):41-46. 被引量:52
  • 3何善庆.GIS中的快速暂态过程[J].高压电器,1993,30(1):47-50.
  • 4电力科学研究院系统所.广东大亚湾核电站400/500kV开关站操作过电压研究北京:电力科学研究院内部报告[R].,1993..
  • 5Ogawa S, Haginmori E, Nishiwaki S, et al. Estimation of restriking transient over-voltage on disconnecting switch for GIS [J]. IEEE T-PWRD, 1986, 1(2): 95-102.
  • 6Ozawa J, Yamagiwa T, Hosokawa M, et al. Suppression of fast transient over-voltage during gas disconnector switching in GIS [J]. IEEE T-PWRD, 1986, 1(4): 194-201.
  • 7Povh D, Schmitt H, Volcker O, et al. Modeling and analysis guidelines for very fast transients [J]. IEEE T-PWRD,1996, 11(4): 2028-2035.
  • 8Fujita S, Hosokawa N, Shibuya Y, et al. Experimental investigation of high frequency voltage oscillation in transformer windings [J]. IEEE T-PWRD, 1998, 13(4):1201 - 1207.
  • 9Nakanishi K, Fujita S, Kurita H, et al. High frequency voltage oscillation in transformer windings and electrical breakdown properties of inter-turn insulation immersed in oil at VFT voltage [A]. IEEE Annual Report-Conference on Electrical Insulation and Dielectric Phenomena [C].Minneapolis, 1997. 490- 493.
  • 10Shibuya Y, Fujita S, Shimomura T. Effects of very fast transient over-voltages on transformer [J].IEE Proceedings, Part C, 1999, 146(4): 459-464.

共引文献134

同被引文献258

引证文献25

二级引证文献117

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部