期刊文献+

德宝工程紧急直流功率支援策略研究 被引量:1

Research on Emergency DC Power Support Strategy in Debao Project
在线阅读 下载PDF
导出
摘要 以直流输电线路异步联接的两个交流系统为模型,分析了紧急直流功率支援的机理。通过将其等效为一个单机无穷大系统,利用扩展等面积法则推理可知,系统正摆时提升直流功率,回摆时回降直流功率可分别达到吸收和补偿交流系统中有功过剩和缺额的目的,提高系统的暂态性能。在此结论上,针对德宝直流异步联接的四川—西北电网2010年丰大方式,在BPA仿真平台上研究了四川电网交流线路短路故障、无故障切机、无故障甩负荷情况下的德宝紧急直流功率支援策略。研究表明,对于交流线路短路故障,宜采用大方式调制策略;而对于无故障切机和无故障甩负荷故障,则应采用功率回降(或提升)结合大方式调制的策略。 The mechanism of emergency DC power support(EDCPS) is analyzed based on a model which two AC systems are connected by a HVDC link.This model can be equivalent to one machine infinite bus(OMIB)system,and the extended equal area criterion(EEAC)shows that step-up(or step down) DC power when it swings up(or swings down) can absorb(or compensate) active power in AC system which can enhance the transient stability of the system.Based on this conclusion,the summer peak case in 2010 of Sichuan-Xibei Power Grid connected by Debao HVDC link is studied,including short-circuit fault of AC lines,trouble-free machine cutting and trouble-free load rejection in Sichuan Power Grid.The results prove that the high level modulation fits for the first fault,while the strategy combining power back down(or upgrade) with high level modulation is suitable for the latter two faults.
作者 贺洋
出处 《四川电力技术》 2011年第1期1-4,32,共5页 Sichuan Electric Power Technology
基金 国家科技支撑计划资助项目(2008BAA13B01) 国家电网公司科技项目
关键词 德宝直流 紧急直流功率支援 功率提升/回降 大方式调制 功角稳定 Debao HVDC link emergency DC power support power upgrade/back down high level modulation angle stability
  • 相关文献

参考文献12

  • 1Hammons T J, Woodford D, Loughtan M, et al. Role of HVDC Transmission in Future Energy Development [ J]. IEEE Power Engineering Review,2000,20(2 ) :10- 25.
  • 2舒印彪.中国直流输电的现状及展望[J].高电压技术,2004,30(11):1-2. 被引量:238
  • 3谢惠藩,张尧,夏成军.特高压紧急直流功率支援策略研究[J].电力自动化设备,2008,28(8):1-7. 被引量:41
  • 4Nikamal Fernandopulle. Improved Dynamic Security Assessment for AC/DC Power Systems Using Energy Functions [ J]. IEEE Transactions on power systems,2003,28 (4) :1470 - 1477.
  • 5任景.交直流互联系统送端孤网运行时频率稳定问题研究[D].成都:四川大学,2008.
  • 6S. Corsi, A. Danelli, M. Pozzi. Emergency-stability Controls through HVDC Links [ C ]. Power Engineering Society Summer Meeting, Chieago - USA, 2002 ( 2 ) : 774 - 779.
  • 7Reeve J, Lane- Smith S P. Multi- infeed HVDC Transient Response and Recovery Strategies [ J]. IEEE Trans on Power Delivery, 1993,8 (4) : 1995 - 2001.
  • 8Prabha Kundur. Power System Stability and Control [ M]. New York : McGraw - Hill, 1993.
  • 9房大中,杨晓东,宋文南.提高交直流电力系统稳定性的HVDC模糊逻辑控制器[J].电力系统自动化,2002,26(6):23-27. 被引量:17
  • 10刘红超,李兴源,王路,陈凌云,邱晓燕.多馈入直流输电系统中直流调制的协调优化[J].电网技术,2004,28(1):5-9. 被引量:60

二级参考文献39

共引文献373

同被引文献17

引证文献1

二级引证文献10