小电流接地系统4PT消谐问题的探讨 被引量:6

Discussion on the Common Problem of Anti-Resonance Using 4 PT in the Neutral Node Ungrounded Power System
在线阅读 下载PDF
导出
摘要 在小电流接地系统中,由于PT励磁电感的非线性特性,在一定条件下容易产生铁磁谐振过电压,给系统的安全运行带来严重隐患。近年来,供电系统大都用在PT中性点串接第四支PT的方法来消除其谐振。随着智能电网目标的提出,消谐PT二次接线不统一的特点亟待解决,同时也影响了运行人员的正确判断。重点分析几种目前常见的PT消谐的原理,运行时的注意事项,为以后整改及优化提供一定的依据。 In the neutral node ungrounded power system,ferroresonance due to the nonlinear excitation inductance of three-phase inductive potential transformer(PT) once happened,has a serious impact on the safe operation of power system.In recent years,connecting single-phase PT to the neutral point of three-phase PT high voltage side is used by most power systems.With the proposed of Smart Grid,the non-normative connection mode of secondary circuits of the anti-resonance PT is urgent to solve,it also affects the judgment of the operators.This paper mainly analyses the common anti-resonance PT of working principles and considerations in operation,offers references for optimization and rectification of the anti-resonance PT.
机构地区 郑州供电公司
出处 《华中电力》 2010年第5期43-46,51,共5页 Central China Electric Power
关键词 小电流接地系统 消谐 电压互感器 接线方式 the neutral node ungrounded power system ferroresonance elimination potential transformer wirings' connections