期刊文献+

Calculation of fire extinguishment time with water mist in an enclosed room 被引量:2

Calculation of fire extinguishment time with water mist in an enclosed room
原文传递
导出
摘要 The fire extinguishment time is a major factor to evaluate the efficiency of fire extinguishment with water mist. In this paper the fire extinguishment time with water mist in an enclosed room is calculated. Before adding water mist, the chemical kinetics plays the role in combustion, where a dimensionless math model is established by us-ing the Semenov theory. After adding water mist, the diffusion plays the role instead. Then another math model containing water mist and dominated by oxygen concentration is established. The fire temperature is integrated from Tm to extinguishment temperature TB and the extinguishment time can be obtained. The calculated values are compared with the experimental data under different conditions. The results show that this model can predict the fire extinguishment time accurately. Besides, this model also can be used to determine the critical water mist flux and evaluate which fire extinguishment mechanisms dominate the extinguishment.
出处 《Journal of Thermal Science》 SCIE EI CAS CSCD 2010年第6期561-566,共6页 热科学学报(英文版)
关键词 extinguishment time minimum flux water mist 细水雾灭火 消防灭火 计算值 时间 房间 封闭 数学模型 化学动力学
  • 相关文献

参考文献10

  • 1National Fire Protection Association. NFPA 750 Standard for Water Mist Fire Suppression Systems, Quincy, MA, USA: NFPA, (2000).
  • 2Alpert, R. L.: Incentives for use of misting sprays as a fire suppression flooding agent, In Water Mist Fire Suppression on Workshop Proceedings, NISTIR 5207, National Institute of Standards and Technology, Gaithersburg, MD, pp.31-35, (1993).
  • 3Mawhinney, J. R. and Solomon, R.: Water Mist Fire Suppression Systems, In The Fire Protection Handbook, 18th ed., edited by A.E. Cote, Boston, National Fire Protection Association, pp.216-248, (1997).
  • 4Richard, J., Garo, J. P., Souil, J. M., Vantelon, J. E: On the flame structure at the base of a pool fire interacting with a water mist, Exp. Therm. and Fluid Science, vol.27, pp.439-448, (2003).
  • 5Back, G. G., Beyler, C. L., Hansen, R.: A quasi-steadystate model for predicting fire suppression in spaces protected by water mist systems, Fire Safety Journal, vol.35, pp.327-362, (2000).
  • 6Vulis, L. A.: Thermal Regimes of Combustion, McGraw- Hill, N.Y., (1961).
  • 7Li, Y. F. and Chow, W. K.: Modelling of water mist fire suppression systems by a one-zone model, Combustion Theory and Modelling, vol.8, pp.567-592, (2004).
  • 8Semenov, N. N.: Z. Phys., vol.48, pp.571, (1928).
  • 9Guidelines for the Approval of Fixed Water-Based Local Application Fire- Fighting Systems, IMO MSC/Circ 1165, London, (2005.6.10).
  • 10Water Mist Nozzles for fire Protection Service, UL 2167, (2004.2.20).