摘要 污水源热泵系统的节能减排效益显著,污水的管内换热特性急需掌握。基于污垢热阻法建立光滑铜管管内污垢生长特性试验台,试验得出了人工污水颗粒状污垢管内的生长特性,并建立了其渐近型污垢积聚预测模型。试验发现,该人工污水在光滑铜管结垢的诱导期为21 h,污垢热阻稳定时间为95 h,稳定污垢热阻为1.5×10-5m2.K/W。 The merits of the sewage source heat pump system are remarkable on energy efficiency and pollution reduction. Based on the fouling resistance law, the test bench was established on growth characteristics of fouling in copper pipe. The experiment has been carried on and the growth characteristics of fouling in copper pipe were obtained with the asymptotic agglomeration forecast model. It is found that the fouling induction period of the sewage is 21 hours in the smooth copper pipe, the fouling resistance settling time is 95 hours, and the stable fouling resistance is for ×10^-5m^2·K/W.
出处 《土木建筑与环境工程》 CSCD 北大核心 2010年第5期60-64,共5页 Journal of Civil,Architectural & Environment Engineering
基金 中国博士后科学基金资助项目(20100471447) 大连市优秀青年科技人才基金(2008J23JH024)
关键词 污水 铜管 颗粒状污垢 热阻法试验 sewage, copper pipe, granular fouling, fouling resistance law experiment
  • 相关文献

参考文献15

  • 1LINDSTROM H O. Experiences with a 3.3 MW heat pump using sewage water as heat source[J]. Journal of Heat Recovery Systems, 1985, 5(1):33- 38.
  • 2CADDET. First DHC System in Japan Using Untreated Sewage as a Heat Source[R]. 1997, 112-125.
  • 3ARASHI NORIO, INABA ATSUSHI. Evaluation of energy use in district heating and cooling plant using sewage and one using air as heat source[J]. Journal of the Japan Institute of Energy, 2000, 79(5): 446-454.
  • 4YOSHII T. Technology for utilizing unused low temperature difference energy[J]. Journal of the Japan Institute of Energy, 2001, 80(8): 696 -706.
  • 5FUNAMIZU N, LIDA M, SAKAKURA Y. Reuse of heat energy in waste water: implementation examples in Japan[J]. Water Science and Technology, 2001, 43 (10) : 277-286.
  • 6QIAN J F, SUN D X. Optimization and analysis of the urban sewage source heat pump system by finite time thermodynamics theory [C]//Proceedings of the 5th International Symposium on Heating, Ventilating and Air Conditioning. Tsinghua University, Beijing, 2007: 923-926.
  • 7BAEK N C, SHIN U C, YOON J H. A study on the design and analysis of a heat pump heating system using wastewater as a heat source[J]. Solar Energy, 2005, 78: 427-440.
  • 8CADDET. Reduced Fouling of Sewage Water Heat Pumps[R]. 1995 : 156-188.
  • 9周文忠.污水源热泵空调系统在污水处理厂的应用[J].暖通空调,2005,35(1):83-86. 被引量:25
  • 10吴荣华,刘志斌,黄磊,孙德兴,任南琪.污水及地表水地源热泵系统规范化设计研究[J].暖通空调,2006,36(12):63-69. 被引量:21