期刊文献+

R417A热泵空调器运行特性分析 被引量:1

Analysis of Running Performance of Heat Pump Type Air Conditioner Using R417A
在线阅读 下载PDF
导出
摘要 在焓差实验台和热泵性能测试系统中,对1台R417A热泵空调器在高/低温工况下的运行特性进行研究。通过改变蒸发器侧空气的温度、湿度等参数,测定了不同工况下空调器的各项性能指标。结果显示R417A热泵空调器的排气温度相对较低,制冷系统的冷凝温度、蒸发温度、制热系数和功耗在高温工况时变化不大,低温工况时,由于室外侧翅片管蒸发器结霜系统各性能变化较大,在结霜后期系统的性能有较大的衰减。 Using air-enthalpy test box and heat pump performance test system,evaluates the running performance of a R417A air-conditioner at high and low temperature condition with.By changing the temperature and humidity of the air on the evaporator side,records the temperature in and out the compressor,evaporation and condensation temperature,COP,and races dynamically the frost formation process on the flat-fin surface of an outdoor heater exchanger with a numeral camera.The results show that the outlet temperature of compressor at the high and low temperature condition is much lower in the R417A air condition,the changing of the condensation temperature,evaporation temperature,COP and power consumed at high temperature condition is less,the change of every aspect at low temperature condition is biggest because the frost on the flat-fin surface,the performance of the air-conditioner at the end of frost period is much worse.
机构地区 上海理工大学
出处 《流体机械》 CSCD 北大核心 2010年第9期83-86,55,共5页 Fluid Machinery
基金 上海市重点学科建设项目(S30503)
关键词 R417A 翅片管蒸发器 运行特性 结霜 R417A fin-and-tube evaporator running performance frost
  • 相关文献

参考文献7

二级参考文献51

  • 1徐雪琴.我国R22逐步禁用和替代物的现状与进展[J].制冷技术,2004,24(4):12-15. 被引量:10
  • 2James M.Calm,Piotr A.Domanski,张建君.R-22的替代现状[J].制冷与空调,2005,5(1):62-69. 被引量:13
  • 3[3]J.D.Douglas,J.E.Braum,E.A.Groll,D.R.Tree.A cost-based method for comparing alternative refrigerants applied to R22 system. International Journal of Refrigeration,1999,22:107~125
  • 4[6]Gallagher J.S, Mclinden M O, Morrision G.Thermodynamic Diagrams for Refrigerant Mixtures. ASHRAE Trans,1988, 95:2119~2134
  • 5吴勇华.CFC替代工质研究现状及其发展方向[J].五邑大学学报(自然科学版),1997,11(1):71-77. 被引量:2
  • 6Calm, J. M. , and G. C. Hourahan. 2001. "Refrigerant Data Summary. " Engineered Systems 18(11):74-88.
  • 7Domanski, P. A., 1995. "Minimizing Throttling Llosses in the Refrigeration Cycle. " Proceedings of the International Congress of Refrigeration pp. 766-773. Paris, France: International Institute of Refrigeration.
  • 8Domanski, P. A. , D. A. Didion, and J. S. W. Chi. 2003. CYCLE-D: NIST Vapor-Compression Design Program (version 3.0), Standard reference database 49. Gaithersburg, MD: National Institute of Standards and Technology (NIST).
  • 9IPCC. 2001. Climate Change 2001 : The Scientific Basis - Contribution of Working Group I to the IPC~ Third Assessment Report. Intergovernmental Panel on Climate Change(IPCC) of the World Meteorological Organization (WMO) and the United Nations Environment Programme(UNEP). Edited by J. T. Houghton, Y. Ding, D. J. Griggs, M. Noguer, P. J. van der Linden, X. Dai, K. Maskell, and C. A. Johnson. Cambridge, UK: Cambridge University Press.
  • 10Kul I. ,D. D. DesMarteau,and A. L. Beyerlein. 2004. "Coefficient of performance of fluorinated ether and fluorinated ethermixtures, "paper 4711, ASHRAE Transactions 110 (2).

共引文献63

同被引文献15

  • 1James M.Calm,Piotr A.Domanski,张建君.R-22的替代现状[J].制冷与空调,2005,5(1):62-69. 被引量:13
  • 2张明方,李鹏荣.R417A替代家用空调器用R22的实验研究[J].制冷与空调,2006,6(5):80-82. 被引量:10
  • 3李雪,高强,孙平.R417A的应用现状与展望[J].制冷与空调,2007,7(4):59-61. 被引量:10
  • 4中国国家标准化管理委员会.GB/T 7725-2004 房间空气调节器[S],2004
  • 5Arpea C, Renno C. Experimental comparison of R22 with R417A performance in a vapor compression re- frigeration plant subjected to a cold store [ J ]. Energy Conversion and Management, 2004,32(4) :43-47.
  • 6Arpea C, Mastrullo R, Renno C. An analysis of the performance of a vapor compression plant working both as a water chiller and a heat pump using R22 and R417A [ J ]. Applied Thermal Engineering, 2004, 24: 487-499.
  • 7Arpea C, Renno C. Experimrntal comparison of R22 with R417A performance in a vapor compression re- frigeration plant subjected to a cold store[ J]. Energy Conversion and Management, 2004, 45 : 1807-1819.
  • 8Roberts N A. Use of R417A(ISCEON 59) in Refrige- ration and Air Conductioning Appliancations [ J/OL]. http ://www. eurocooling, corn/articlerhodia, htm.
  • 9郭永新.R417A冷媒替代R22冷媒之应用现况[R].Rhodia报告:1990.
  • 10张太康,翁文兵,喻晶.R134a、R417a和R22用于空气源热泵热水器的性能研究[J].流体机械,2010,38(5):72-76. 被引量:31

引证文献1