疏水扩容器减温水管道强烈振动和高噪声分析 被引量:1

ANALYSIS OF VIOLENT VIBRATION AND HIGH NOISE OCCURRED ON DESUPERHEATING WATER PIPE-LINE TO DRAIN FLASH TANK
在线阅读 下载PDF
导出
摘要 华能珞璜发电有限公司(珞璜电厂)三期2×600 MW机组疏水扩容器减温水管道存在强烈振动和高噪声的现象,试验分析认为,减温水喷管喷孔孔径偏大是造成减温水管道产生振动和高噪声的主要原因。通过对减温水喷管的喷孔数和孔径进行改进,成功消除了减温水管道的强烈振动和高噪声的问题。 The phenomena of violent vibration and high noise occurred on desuperheating water pipeline to the drain flash tank of 2 × 600 MW units in second - phase project of Huaneng Luohuang Power Generation Co Ltd have been analysed,it is believed from test and analysis that the main cause resulting in violent vibration and high noise on desuperheating water pipeline is the larger aperture of desuperheating water spraying pipe. Through retrofitting the number and apecture of spray - holes on the desuperheating water spraying pipe, the problem of violent vibration and high noise occurred on the desuperbeating water pipeline has been successfully eliminated.
出处 《热力发电》 CAS 北大核心 2010年第4期95-96,共2页 Thermal Power Generation
关键词 600 MW火电机组 疏水扩容器 减温水管道 强烈振动 高噪声 600 MW unit drain flash tank desuperheating water pipeline violent vibration high noise