深圳市地铁一号线运营前空气中和空调系统微生物污染情况 被引量:13

Microbial Contamination in The Air and Air-conditioning System of Subway Line One of Shenzhen City before Operation
原文传递
导出
摘要 目的掌握深圳地铁运营前卫生状况本底资料。方法依照相关方法,对深圳市地铁1号线延长站环境空气及空调系统的样本进行检测分析。结果检测地铁站空气样本504份,细菌总数、β-溶血性链球菌合格率分别为100%、98%;检测地铁站空调系统样本237份,空调送风细菌总数、真菌总数、β-溶血性链球菌合格率分别为43%、47%、97%;风管内表面的细菌总数、真菌总数、β-溶血性链球菌合格率分别为100%、100%、100%;12份冷却水未检出嗜肺军团菌。结论地铁站空调系统微生物污染程度较重,地铁站空气及空调系统中存在β-溶血性链球菌,建议地铁公司在运营前做好对地铁站空气和空调系统的消毒工作,以确保乘客的健康。 [Objective]To master the sanitation status of subway stations in Shenzhen before operation.[Methods]In accordance with the relevant methods,the samples of ambient air and air-conditioning system in extension of Subway Line 1 station were analyzed.[Results]In 504 air samples,The qualification rates in total bacteria count,β-hemolytic streptococcus were 100%,98%. In 237 samples from air-conditioning systems,the qualification rates of total bacteria count,total epiphyte count,β-hemolytic streptococcus in wind deliveries of air conditioning systems,were 43%,47%,98%. The qualification rates of total bacteria count,total epiphyte count,β-hemolytic streptococcus in inner surface of air conditioning systems,were 100%,100%,97%. No Legionella pneumophila was detected in 12 cooling water samples.[Conclusion]The microbial contamination of is serious in the air and air-conditioning system of subway station,with β-hemolytic streptococcus existence. It is suggested that the subway corporation should disinfect the air and air conditioning systems of subway stations before operation to protect the health of passengers.
出处 《职业与健康》 CAS 2010年第7期796-797,共2页 Occupation and Health
关键词 地铁 空调系统 细菌总数 真菌总数 Β-溶血性链球菌 Subway Air-conditioning Total bacteria count Total epiphyte count β-hemolytic streptococcus
  • 相关文献

参考文献4

二级参考文献10

共引文献23

同被引文献167

引证文献13

二级引证文献61

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部