摘要 为进一步揭示变压器油浸绝缘纸老化机理,对变压器常用矿物油-纸复合绝缘在110°C下进行了300 d的加速热老化实验。利用热重和差示扫描量热两种热分析方法对油浸绝缘纸的热裂解过程及裂解机理进行了分析,研究了不同老化程度的油浸绝缘纸的热解特性及动力学参数的变化规律。结果表明,不同老化程度的油浸绝缘纸热裂解机理未发生变化;随着绝缘纸老化程度的加深,绝缘纸的热稳定性变差;在绝缘纸老化过程中,绝缘纸热裂解活化能先增加再减小,绝缘纸热焓值呈一直增大趋势,可将绝缘纸热焓值作为判断绝缘纸老化程度的参量之一。 In order to reveal ageing mechanisms of transformer oil-immersed paper,oil-paper insulation accelerating thermal ageing was test at 110°C,and the thermogravimetry(TG) and differential scanning calorimeter(DSC)analyses were applied to study the thermo-decomposing processes and mechanisms of different degree of ageing sample.The result show that different ageing degrees of oil-immersed paper have the same thermo-decomposing mechanism;the thermal stability of paper decreases with ageing;throughout the ageing process,pyrolysis activation energy increases at first and then declines;moreover,a good exponential relation between degree of polymerization and the enthalpy is found,so the paper enthalpy can be used as one of paramerters for evaluating ageing grade of insulation.
出处 《高电压技术》 EI CAS CSCD 北大核心 2010年第3期572-577,共6页 High Voltage Engineering
基金 国家重点基础研究发展计划(973计划)(2009CB724505-1)~~
关键词 变压器 油浸绝缘纸 热重分析 差示扫描量热分析 活化能 热焓 transformer oil-immersed paper thermogravimetry differential scanning calorimeter activation energy enthalpy
  • 相关文献

参考文献18

  • 1Shroff D H, Stannett A W. Review of paper ageing in power transformers[J]. IEE Proceedings- C: Generation, transmission and Distribution, 1985, 132(6): 312-319.
  • 2杨丽君,廖瑞金,孙会刚,孙才新,李剑.油纸绝缘热老化特性及生成物的对比分析[J].中国电机工程学报,2008,28(22):53-58. 被引量:91
  • 3Emsley A M, Stevens G C. Review of chemical indicators of degradation of cellulosic electrical paper insulation in oil-filled transformers [ J ]. IEE Proceedings - Science Measurement Technology, 1994, 141(5):324-333.
  • 4Hill D G T, Le T T, Darveniza M, et al. Study of degradation of cellulosic insulation materials in a power transformer, part 1 : molecular weight study of cellulose insulation paper[J]. Polymer Degradation and Stability, 1995, 49(1):79-87.
  • 5Hill D G T, Le T T, Darveniza M, et al. Study of degradation of cellulosic insulation materials in a power transformer, part 2: tensile strength of cellulose insulation paper[J]. Polymer Degradation and Stability, 1995, 49(3): 429-435.
  • 6Emsley A M, Xiao X, Heywood R J, et al. Degradation of cellulosic insulation in power transformers, part 3: effects of oxygen and water on ageing in oil[J]. lEE Proceedings-Science Measurement and Technology, 2000, 147(3): 115-119.
  • 7翁秀兰.热分析技术及其在高分子材料研究中的应用[J].广州化学,2008,33(3):72-76. 被引量:30
  • 8鲍棋铭,高乃奎,马小芹,张亮,谢恒堃.大型发电机主绝缘老化的热分析研究[J].中国电机工程学报,2003,23(7):99-101. 被引量:21
  • 9谭亮红,董理,林达文,王进,周淑华,周志诚.CR硫化胶老化过程中热性能和动态力学性能变化的研究[J].橡胶工业,2005,52(4):244-246. 被引量:6
  • 10Soares S, Camino G, Levchik S. Comparative study of the thermal decomposition of pure cellulose and pulp paper[J]. Polymer Degradation and Stability, 1995, 49(2): 275-283.