期刊文献+

考虑故障阻抗与多级变压器影响的电压凹陷评估 被引量:13

Voltage sag assessment considering fault impedance and cascaded transformers
在线阅读 下载PDF
导出
摘要 综合考虑了故障阻抗的随机性和不同绕组联接方式的多级变压器对凹陷评估的影响。建立了故障阻抗的随机分布模型和多级变压器的等效移相矩阵,对考虑2个方面影响因素后的电压凹陷幅值与频次评估的数学模型、算法和步骤进行了详细研究。对简单9节点系统和IEEE30节点系统进行了仿真分析,结果证明,变压器绕组联接方式对电压凹陷幅值和频次均有影响,故障阻抗对电压凹陷幅值有明显影响,与现有评估方法进行比较,评估结果准确,原理简单,适用于任意规模与结构形式的电网。 The influences of the fault impedance randomieity and the cascaded transformers with different connection modes on the voltage sag assessment are studied. The stochastic probability model of fault impedance and the equivalent phase shift matrix of cascaded transformers are proposed. The mathematic models,arithmetic and approaches of voltage sag magnitude and frequency assessment are researched with the consideration of both influences. Simulative analysis is carried out for 9-node network and IEEE-30 test system,which shows that,the transformer connection mode has influence on both voltage sag magnitude and frequency while fault impedance has obvious influence on voltage sag magnitude. Compared with exiting methods,the proposed method is simple and accurate,suitable for power system of any scale and structure.
出处 《电力自动化设备》 EI CSCD 北大核心 2010年第2期43-47,52,共6页 Electric Power Automation Equipment
基金 国家自然科学基金项目(50877049,50677041) 四川省应用基础研究项目(2008JY0043-2)~~
关键词 电压凹陷 凹陷传播 故障阻抗 随机模型 等效相移矩阵 voltage sag sag propagation fault impedance stochastic model equivalent phase shift matrix
  • 相关文献

参考文献20

  • 1IEEE Standards Board. IEEE Std 1159-1995 IEEE recommended practice for monitoring Electric Power Quality [S]. New York, USA: IEEE, 1995.
  • 2BOLLEN M H J. Understanding power quality problems:voltage sags and interruptions[M]. Piscataway,NJ,USA:IEEE Press,2000: 139-170.
  • 3MCGRANAGHAN M F,MUELLER D R,SAMOTYJ M J. Voltage sags in industrial systems[J]. IEEE Trans Industry Applications, 1993,29 (2) : 397-402.
  • 4肖先勇,王希宝,薛丽丽,刘波,杨洪耕.敏感负荷电压凹陷敏感度的随机估计方法[J].电网技术,2007,31(22):30-33. 被引量:53
  • 5CHAN J Y,MILANOVIC J V. Methodology for assessment of financial losses due to voltage sags and short interruptions[C]// 9th International Conference on Electrical Power Quality and Utilisation, EPQU 2007. Barcelona, Spain : IEEE, 2007 : 1-6.
  • 6MENDES W R,SAMESIMA M I,MOURA F A, Influence of power transformer winding connections on the propagation of voltage sags through electric system [C ]//5th International Conference on the European Electricity Market(EEM 2008). Lisbon, Portugal :IEEE ,2008 : 1-6.
  • 7FILHO J M C,ABREU J P G,LEBORGNE R C,et al. Comparative analysis between measurements and simulations of voltage sags [C] //Harmonics and Quality of Power,2002.10th International Conference on. Rio de Janeiro, Brazil :IEEE, 2002:435-440.
  • 8BOLLEN M H J. Method of critical distances for stochastic assessment of voltage sags[J]. IEE Proceedings Generation,Transmission & Distribution, 1998,145(1) :70-76.
  • 9QADER M R,BOLLEN M H J. Stochastic prediction of voltage sags in a large transmission system[J]. IEEE Trans on Industry Applications, 1999,35 ( 1 ) : 152-162.
  • 10MOSCHAKIS M N,HATZIARGYRIOU N D. Analytical calculation and stochastic assessment of voltage sags[J]. IEEE Trans on Power Delivery,2006,21 (3) : 1727-1734.

二级参考文献24

共引文献76

同被引文献152

引证文献13

二级引证文献87

相关作者